# RS485 to Ethernet Module Installation Guide
## Overview
This guide provides step-by-step instructions for installing a 2-Channel RS485 to Ethernet adapter module to connect Modbus devices (thermostats) to a network.
## Hardware Requirements
- 2-CH RS485 to Ethernet adapter module
- Existing 24V DC transformer
- RS485/Modbus devices (e.g., thermostats)
- Appropriate wiring (shielded twisted pair recommended for RS485)
## Module Specifications
- **Power Input**: 6-36V DC (24V DC typical)
- **RS485 Channels**: 2 independent channels
- **Ethernet Ports**: 2 ports (either can be used for network, other for cascading)
## Connection Diagram
### Power Connections
```
24V DC Transformer RS485 Module
┌─────────────┐ ┌──────────────────┐
│ │ │ │
│ + 24V ───┼────────────┼──→ 6-36V Input │
│ │ │ │
│ - GND ───┼────────────┼──→ Ground │
│ │ │ │
└─────────────┘ └──────────────────┘
```
### RS485 Data Connections
```
Electrical Panel RS485 Module
XCOM Terminal Group
┌──────────────────────┐ ┌─────────────────────┐
│ │ │ │
│ Device 1 (String 1) │ │ RS485 Channel 1 │
│ ├─ T+ (Data+) ──────┼───────────┼──→ A │
│ ├─ T- (Data-) ──────┼───────────┼──→ B │
│ └─ GND ─────────────┼───────────┼──→ Signal Ground │
│ │ │ │
│ Device 2 (String 2) │ │ RS485 Channel 2 │
│ ├─ T+ (Data+) ──────┼───────────┼──→ A │
│ ├─ T- (Data-) ──────┼───────────┼──→ B │
│ └─ GND ─────────────┼───────────┼──→ Signal Ground │
│ │ │ │
└──────────────────────┘ └─────────────────────┘
```
### Complete System Overview
```
┌─────────────────┐
│ 24V DC Power │
│ Transformer │
└────────┬────────┘
│
┌────────▼──────────────────────────┐
│ RS485 to Ethernet Module │
│ │
│ Power: 6-36V Input, Ground │
│ │
│ RS485-1: A, B, GND │
│ RS485-2: A, B, GND │
│ │
│ Ethernet: ETH1 or ETH2 ────────► To Network
│ │
└──────┬─────────────┬──────────────┘
│ │
┌─────────▼─────┐ ┌───▼────────────┐
│ Thermostat │ │ Thermostat │
│ String 1 │ │ String 2 │
│ (via Modbus) │ │ (via Modbus) │
└───────────────┘ └────────────────┘
```
## Installation Steps
### 1. Safety First
⚠️ **IMPORTANT**: Disconnect all power before beginning installation.
### 2. Power Connection
1. Locate the existing 24V DC transformer
2. Connect the module's **6-36V Input** terminal to the transformer's **+ (positive)** output
3. Connect the module's **Ground** terminal to the transformer's **- (negative)** output
**Wire colors (typical)**:
- Red: +24V DC
- Black: Ground/Common
### 3. RS485 Data Connections
#### Understanding the XCOM Terminal Group
In your electrical panel's XCOM group, you'll find:
- First set of wires: RDZ HMI connections
- Following pairs: Two RS485 pairs for two strings of thermostats
#### Connection Notes
- **T+** on devices connects to **A** on the module
- **T-** on devices connects to **B** on the module
- **PE/GND** connects to **Signal Ground** on the module
- Some wires may be unmarked - verify with continuity testing
#### Wiring Each Channel
Connect each RS485 device string to one of the two module channels:
**For String 1** (any channel - e.g., RS485-1):
```
Device T+ ──→ RS485-1 A
Device T- ──→ RS485-1 B
Device GND ─→ RS485-1 Signal Ground
```
**For String 2** (remaining channel - e.g., RS485-2):
```
Device T+ ──→ RS485-2 A
Device T- ──→ RS485-2 B
Device GND ─→ RS485-2 Signal Ground
```
> **Note**: The assignment of devices to Channel 1 or Channel 2 is flexible. Choose either channel for each device string - the specific mapping doesn't matter as thermostat identification is done after discovery through the network.
### 4. Verify Connections
**Before applying power**:
1. ✅ Check continuity between Wi-SA connectors and module terminals
2. ✅ Verify correct polarity on power connections
3. ✅ Ensure RS485 wires are properly paired (A-to-A, B-to-B)
4. ✅ Confirm all ground connections are secure
### 5. Ethernet Connection
1. Connect an Ethernet cable from either **ETH1** or **ETH2** to your network switch/router
2. The second Ethernet port can be used for router cascading if needed
### 6. Power On and Test
1. Restore power to the 24V DC transformer
2. Check the module's LED indicators:
| LED | Description |
|-----|-------------|
| **PWR** | Power indicator - should be solid |
| **NET** | Network indicator - blinks when connected to Ethernet |
| **LINK1** | Lights up when establishing RS485 Channel 1 connection |
| **ACT1** | Lights up when Channel 1 is transmitting data |
| **LINK2** | Lights up when establishing RS485 Channel 2 connection |
| **ACT2** | Lights up when Channel 2 is transmitting data |
## Important Notes
- ⚠️ Use **shielded twisted pair cable** for all RS485 connections to minimize interference
- ⚠️ Maintain proper polarity: A↔A (T+), B↔B (T-), GND↔GND
- ⚠️ Power input must be within **6-36V DC** range (24V DC is typical)
- ⚠️ Either Ethernet port functions identically - choose whichever is more convenient
- ℹ️ Channel assignment is flexible - devices can be connected to either RS485-1 or RS485-2
- ℹ️ Device discovery and mapping is performed after installation via network configuration
## Troubleshooting
| Issue | Possible Solution |
|-------|------------------|
| PWR LED not lit | Check 24V DC power connections and voltage |
| NET LED not blinking | Verify Ethernet cable and network connection |
| LINK LED not lit | Check RS485 wiring polarity (A, B, GND) |
| No device communication | Verify continuity of RS485 cables; check for proper termination |
## Post-Installation
After successful installation:
1. Access the module's web interface via its IP address
2. Configure network settings if necessary
3. Perform device discovery to identify all connected Modbus devices
4. Map thermostats/devices to their physical locations
5. Test communication with each device
## Safety and Compliance
- Installation should be performed by a **qualified electrician**
- Follow all local electrical codes and regulations
- Ensure proper grounding of all equipment
- Use appropriate wire gauges for the application
## Additional Resources
- Consult the module's technical documentation for advanced configuration
- Refer to device-specific manuals for RS485 settings (baud rate, parity, etc.)
---