# RS485 to Ethernet Module Installation Guide
|
||
|
||
## Overview
|
||
|
||
This guide provides step-by-step instructions for installing a 2-Channel RS485 to Ethernet adapter module to connect Modbus devices (thermostats) to a network.
|
||
|
||
## Hardware Requirements
|
||
|
||
- 2-CH RS485 to Ethernet adapter module
|
||
- Existing 24V DC transformer
|
||
- RS485/Modbus devices (e.g., thermostats)
|
||
- Appropriate wiring (shielded twisted pair recommended for RS485)
|
||
|
||
## Module Specifications
|
||
|
||
- **Power Input**: 6-36V DC (24V DC typical)
|
||
- **RS485 Channels**: 2 independent channels
|
||
- **Ethernet Ports**: 2 ports (either can be used for network, other for cascading)
|
||
|
||
## Connection Diagram
|
||
|
||
### Power Connections
|
||
|
||
```
|
||
24V DC Transformer RS485 Module
|
||
┌─────────────┐ ┌──────────────────┐
|
||
│ │ │ │
|
||
│ + 24V ───┼────────────┼──→ 6-36V Input │
|
||
│ │ │ │
|
||
│ - GND ───┼────────────┼──→ Ground │
|
||
│ │ │ │
|
||
└─────────────┘ └──────────────────┘
|
||
```
|
||
|
||
### RS485 Data Connections
|
||
|
||
```
|
||
Electrical Panel RS485 Module
|
||
XCOM Terminal Group
|
||
┌──────────────────────┐ ┌─────────────────────┐
|
||
│ │ │ │
|
||
│ Device 1 (String 1) │ │ RS485 Channel 1 │
|
||
│ ├─ T+ (Data+) ──────┼───────────┼──→ A │
|
||
│ ├─ T- (Data-) ──────┼───────────┼──→ B │
|
||
│ └─ GND ─────────────┼───────────┼──→ Signal Ground │
|
||
│ │ │ │
|
||
│ Device 2 (String 2) │ │ RS485 Channel 2 │
|
||
│ ├─ T+ (Data+) ──────┼───────────┼──→ A │
|
||
│ ├─ T- (Data-) ──────┼───────────┼──→ B │
|
||
│ └─ GND ─────────────┼───────────┼──→ Signal Ground │
|
||
│ │ │ │
|
||
└──────────────────────┘ └─────────────────────┘
|
||
```
|
||
|
||
### Complete System Overview
|
||
|
||
```
|
||
┌─────────────────┐
|
||
│ 24V DC Power │
|
||
│ Transformer │
|
||
└────────┬────────┘
|
||
│
|
||
┌────────▼──────────────────────────┐
|
||
│ RS485 to Ethernet Module │
|
||
│ │
|
||
│ Power: 6-36V Input, Ground │
|
||
│ │
|
||
│ RS485-1: A, B, GND │
|
||
│ RS485-2: A, B, GND │
|
||
│ │
|
||
│ Ethernet: ETH1 or ETH2 ────────► To Network
|
||
│ │
|
||
└──────┬─────────────┬──────────────┘
|
||
│ │
|
||
┌─────────▼─────┐ ┌───▼────────────┐
|
||
│ Thermostat │ │ Thermostat │
|
||
│ String 1 │ │ String 2 │
|
||
│ (via Modbus) │ │ (via Modbus) │
|
||
└───────────────┘ └────────────────┘
|
||
```
|
||
|
||
## Installation Steps
|
||
|
||
### 1. Safety First
|
||
|
||
⚠️ **IMPORTANT**: Disconnect all power before beginning installation.
|
||
|
||
### 2. Power Connection
|
||
|
||
1. Locate the existing 24V DC transformer
|
||
2. Connect the module's **6-36V Input** terminal to the transformer's **+ (positive)** output
|
||
3. Connect the module's **Ground** terminal to the transformer's **- (negative)** output
|
||
|
||
**Wire colors (typical)**:
|
||
- Red: +24V DC
|
||
- Black: Ground/Common
|
||
|
||
### 3. RS485 Data Connections
|
||
|
||
#### Understanding the XCOM Terminal Group
|
||
|
||
In your electrical panel's XCOM group, you'll find:
|
||
- First set of wires: RDZ HMI connections
|
||
- Following pairs: Two RS485 pairs for two strings of thermostats
|
||
|
||
#### Connection Notes
|
||
|
||
- **T+** on devices connects to **A** on the module
|
||
- **T-** on devices connects to **B** on the module
|
||
- **PE/GND** connects to **Signal Ground** on the module
|
||
- Some wires may be unmarked - verify with continuity testing
|
||
|
||
#### Wiring Each Channel
|
||
|
||
Connect each RS485 device string to one of the two module channels:
|
||
|
||
**For String 1** (any channel - e.g., RS485-1):
|
||
```
|
||
Device T+ ──→ RS485-1 A
|
||
Device T- ──→ RS485-1 B
|
||
Device GND ─→ RS485-1 Signal Ground
|
||
```
|
||
|
||
**For String 2** (remaining channel - e.g., RS485-2):
|
||
```
|
||
Device T+ ──→ RS485-2 A
|
||
Device T- ──→ RS485-2 B
|
||
Device GND ─→ RS485-2 Signal Ground
|
||
```
|
||
|
||
> **Note**: The assignment of devices to Channel 1 or Channel 2 is flexible. Choose either channel for each device string - the specific mapping doesn't matter as thermostat identification is done after discovery through the network.
|
||
|
||
### 4. Verify Connections
|
||
|
||
**Before applying power**:
|
||
|
||
1. ✅ Check continuity between Wi-SA connectors and module terminals
|
||
2. ✅ Verify correct polarity on power connections
|
||
3. ✅ Ensure RS485 wires are properly paired (A-to-A, B-to-B)
|
||
4. ✅ Confirm all ground connections are secure
|
||
|
||
### 5. Ethernet Connection
|
||
|
||
1. Connect an Ethernet cable from either **ETH1** or **ETH2** to your network switch/router
|
||
2. The second Ethernet port can be used for router cascading if needed
|
||
|
||
### 6. Power On and Test
|
||
|
||
1. Restore power to the 24V DC transformer
|
||
2. Check the module's LED indicators:
|
||
|
||
| LED | Description |
|
||
|-----|-------------|
|
||
| **PWR** | Power indicator - should be solid |
|
||
| **NET** | Network indicator - blinks when connected to Ethernet |
|
||
| **LINK1** | Lights up when establishing RS485 Channel 1 connection |
|
||
| **ACT1** | Lights up when Channel 1 is transmitting data |
|
||
| **LINK2** | Lights up when establishing RS485 Channel 2 connection |
|
||
| **ACT2** | Lights up when Channel 2 is transmitting data |
|
||
|
||
## Important Notes
|
||
|
||
- ⚠️ Use **shielded twisted pair cable** for all RS485 connections to minimize interference
|
||
- ⚠️ Maintain proper polarity: A↔A (T+), B↔B (T-), GND↔GND
|
||
- ⚠️ Power input must be within **6-36V DC** range (24V DC is typical)
|
||
- ⚠️ Either Ethernet port functions identically - choose whichever is more convenient
|
||
- ℹ️ Channel assignment is flexible - devices can be connected to either RS485-1 or RS485-2
|
||
- ℹ️ Device discovery and mapping is performed after installation via network configuration
|
||
|
||
## Troubleshooting
|
||
|
||
| Issue | Possible Solution |
|
||
|-------|------------------|
|
||
| PWR LED not lit | Check 24V DC power connections and voltage |
|
||
| NET LED not blinking | Verify Ethernet cable and network connection |
|
||
| LINK LED not lit | Check RS485 wiring polarity (A, B, GND) |
|
||
| No device communication | Verify continuity of RS485 cables; check for proper termination |
|
||
|
||
## Post-Installation
|
||
|
||
After successful installation:
|
||
|
||
1. Access the module's web interface via its IP address
|
||
2. Configure network settings if necessary
|
||
3. Perform device discovery to identify all connected Modbus devices
|
||
4. Map thermostats/devices to their physical locations
|
||
5. Test communication with each device
|
||
|
||
## Safety and Compliance
|
||
|
||
- Installation should be performed by a **qualified electrician**
|
||
- Follow all local electrical codes and regulations
|
||
- Ensure proper grounding of all equipment
|
||
- Use appropriate wire gauges for the application
|
||
|
||
## Additional Resources
|
||
|
||
- Consult the module's technical documentation for advanced configuration
|
||
- Refer to device-specific manuals for RS485 settings (baud rate, parity, etc.)
|
||
|
||
---
|
||
|
||
**Revision**: 1.0
|
||
**Last Updated**: January 2026 |