RS485 to Ethernet Module Installation Guide

Overview

This guide provides step-by-step instructions for installing a 2-Channel RS485 to Ethernet adapter module to connect Modbus devices (thermostats) to a network.

Hardware Requirements

  • 2-CH RS485 to Ethernet adapter module
  • Existing 24V DC transformer
  • RS485/Modbus devices (e.g., thermostats)
  • Appropriate wiring (shielded twisted pair recommended for RS485)

Module Specifications

  • Power Input: 6-36V DC (24V DC typical)
  • RS485 Channels: 2 independent channels
  • Ethernet Ports: 2 ports (either can be used for network, other for cascading)

Connection Diagram

Power Connections

24V DC Transformer          RS485 Module
┌─────────────┐            ┌──────────────────┐
│             │            │                  │
│    + 24V ───┼────────────┼──→ 6-36V Input   │
│             │            │                  │
│    - GND ───┼────────────┼──→ Ground        │
│             │            │                  │
└─────────────┘            └──────────────────┘

RS485 Data Connections

Electrical Panel                    RS485 Module
XCOM Terminal Group                 
┌──────────────────────┐           ┌─────────────────────┐
│                      │           │                     │
│  Device 1 (String 1) │           │   RS485 Channel 1   │
│  ├─ T+ (Data+) ──────┼───────────┼──→ A                │
│  ├─ T- (Data-) ──────┼───────────┼──→ B                │
│  └─ GND ─────────────┼───────────┼──→ Signal Ground    │
│                      │           │                     │
│  Device 2 (String 2) │           │   RS485 Channel 2   │
│  ├─ T+ (Data+) ──────┼───────────┼──→ A                │
│  ├─ T- (Data-) ──────┼───────────┼──→ B                │
│  └─ GND ─────────────┼───────────┼──→ Signal Ground    │
│                      │           │                     │
└──────────────────────┘           └─────────────────────┘

Complete System Overview

                    ┌─────────────────┐
                    │  24V DC Power   │
                    │  Transformer    │
                    └────────┬────────┘
                             │
                    ┌────────▼──────────────────────────┐
                    │  RS485 to Ethernet Module         │
                    │                                   │
                    │  Power: 6-36V Input, Ground       │
                    │                                   │
                    │  RS485-1: A, B, GND               │
                    │  RS485-2: A, B, GND               │
                    │                                   │
                    │  Ethernet: ETH1 or ETH2 ────────► To Network
                    │                                   │
                    └──────┬─────────────┬──────────────┘
                           │             │
                 ┌─────────▼─────┐   ┌───▼────────────┐
                 │ Thermostat    │   │ Thermostat     │
                 │ String 1      │   │ String 2       │
                 │ (via Modbus)  │   │ (via Modbus)   │
                 └───────────────┘   └────────────────┘

Installation Steps

1. Safety First

⚠️ IMPORTANT: Disconnect all power before beginning installation.

2. Power Connection

  1. Locate the existing 24V DC transformer
  2. Connect the module's 6-36V Input terminal to the transformer's + (positive) output
  3. Connect the module's Ground terminal to the transformer's - (negative) output

Wire colors (typical):

  • Red: +24V DC
  • Black: Ground/Common

3. RS485 Data Connections

Understanding the XCOM Terminal Group

In your electrical panel's XCOM group, you'll find:

  • First set of wires: RDZ HMI connections
  • Following pairs: Two RS485 pairs for two strings of thermostats

Connection Notes

  • T+ on devices connects to A on the module
  • T- on devices connects to B on the module
  • PE/GND connects to Signal Ground on the module
  • Some wires may be unmarked - verify with continuity testing

Wiring Each Channel

Connect each RS485 device string to one of the two module channels:

For String 1 (any channel - e.g., RS485-1):

Device T+ ──→ RS485-1 A
Device T- ──→ RS485-1 B
Device GND ─→ RS485-1 Signal Ground

For String 2 (remaining channel - e.g., RS485-2):

Device T+ ──→ RS485-2 A
Device T- ──→ RS485-2 B
Device GND ─→ RS485-2 Signal Ground

Note

: The assignment of devices to Channel 1 or Channel 2 is flexible. Choose either channel for each device string - the specific mapping doesn't matter as thermostat identification is done after discovery through the network.

4. Verify Connections

Before applying power:

  1. ✅ Check continuity between Wi-SA connectors and module terminals
  2. ✅ Verify correct polarity on power connections
  3. ✅ Ensure RS485 wires are properly paired (A-to-A, B-to-B)
  4. ✅ Confirm all ground connections are secure

5. Ethernet Connection

  1. Connect an Ethernet cable from either ETH1 or ETH2 to your network switch/router
  2. The second Ethernet port can be used for router cascading if needed

6. Power On and Test

  1. Restore power to the 24V DC transformer
  2. Check the module's LED indicators:
LED Description
PWR Power indicator - should be solid
NET Network indicator - blinks when connected to Ethernet
LINK1 Lights up when establishing RS485 Channel 1 connection
ACT1 Lights up when Channel 1 is transmitting data
LINK2 Lights up when establishing RS485 Channel 2 connection
ACT2 Lights up when Channel 2 is transmitting data

Important Notes

  • ⚠️ Use shielded twisted pair cable for all RS485 connections to minimize interference
  • ⚠️ Maintain proper polarity: A↔A (T+), B↔B (T-), GND↔GND
  • ⚠️ Power input must be within 6-36V DC range (24V DC is typical)
  • ⚠️ Either Ethernet port functions identically - choose whichever is more convenient
  • ℹ️ Channel assignment is flexible - devices can be connected to either RS485-1 or RS485-2
  • ℹ️ Device discovery and mapping is performed after installation via network configuration

Troubleshooting

Issue Possible Solution
PWR LED not lit Check 24V DC power connections and voltage
NET LED not blinking Verify Ethernet cable and network connection
LINK LED not lit Check RS485 wiring polarity (A, B, GND)
No device communication Verify continuity of RS485 cables; check for proper termination

Post-Installation

After successful installation:

  1. Access the module's web interface via its IP address
  2. Configure network settings if necessary
  3. Perform device discovery to identify all connected Modbus devices
  4. Map thermostats/devices to their physical locations
  5. Test communication with each device

Safety and Compliance

  • Installation should be performed by a qualified electrician
  • Follow all local electrical codes and regulations
  • Ensure proper grounding of all equipment
  • Use appropriate wire gauges for the application

Additional Resources

  • Consult the module's technical documentation for advanced configuration
  • Refer to device-specific manuals for RS485 settings (baud rate, parity, etc.)

Revision: 1.0
Last Updated: January 2026