RS485 to Ethernet Module - Software Configuration Guide
Overview
This guide covers the essential software configuration of the 2-CH RS485 to Ethernet adapter. Configuration is done via web browser - no software installation required.
What You Need to Configure
Only two things are critical:
- IP Address - Match your network
- Baud Rate - Set to 19200 (or match your devices)
All other settings can remain at their defaults.
Quick Start
Default Module Settings
- Channel 1:
192.168.1.200 - Channel 2:
192.168.1.201 - Default Port:
4196 - No password required (first login)
Step 1: Access the Web Interface
- Temporarily set your computer's IP to
192.168.1.100(same network as module) - Open web browser and go to:
- Channel 1:
http://192.168.1.200 - Channel 2:
http://192.168.1.201
- Channel 1:
- Click "Login" (leave password blank on first access)
Step 2: Change IP Address
Network Settings section:
- Device IP: Change to your network (example:
192.168.11.200) - Subnet Mask: Usually
255.255.255.0 - Gateway: Your router IP (example:
192.168.11.1) - Leave other settings as default
Important
: Each channel needs a unique IP! Use sequential IPs like
.200and.201
Step 3: Set Baud Rate
Serial Settings section:
- Baud Rate: Set to
19200 - Leave other serial settings as default (8 databits, None parity, 1 stopbit)
Step 4: Save and Repeat
- Click "Submit Modification"
- Access the module at its new IP address
- Repeat Steps 1-4 for Channel 2 with a different IP
Configuration Summary
Essential Settings to Change
| Setting | Channel 1 | Channel 2 |
|---|---|---|
| Device IP | 192.168.x.200 |
192.168.x.201 |
| Baud Rate | 19200 |
19200 |
Other Settings (Keep Defaults)
The web interface shows additional settings that can remain at defaults:
- Work Mode: TCP Server
- Device Port: 4196
- IP mode: Static
- Databits: 8
- Parity: None
- Stopbits: 1
- Flow control: None
- Advanced Settings: Keep defaults
- Multi-Host Settings: Keep defaults
LED Indicators
After configuration, check the module's LEDs:
| LED | Expected Status |
|---|---|
| PWR | Solid (power on) |
| NET | Blinking (network connected) |
| LINK1/2 | On (RS485 connection) |
| ACT1/2 | Blinking (data transmission) |
Troubleshooting
Can't Access Web Interface
- Verify your computer is on
192.168.1.xnetwork - Check Ethernet cable is connected
- Ensure module is powered (PWR LED lit)
- Reset if needed: Hold RESET button for 5 seconds (reverts to
192.168.1.254)
Can't Access After Changing IP
- Update your computer's IP to match the new network
- Verify gateway and subnet mask are correct
- If lost, reset module and start over
No RS485 Communication
- Verify baud rate is set to
19200 - Check RS485 wiring: A to A (T+), B to B (T-)
- Ensure RS485 devices are powered
Configuration Checklist
- Accessed Channel 1 web interface (
192.168.1.200) - Changed Channel 1 IP to match my network
- Set Channel 1 baud rate to
19200 - Saved and verified Channel 1 settings
- Accessed Channel 2 web interface (
192.168.1.201) - Changed Channel 2 IP to match my network (unique from Channel 1)
- Set Channel 2 baud rate to
19200 - Saved and verified Channel 2 settings
- Verified LED indicators are working
Example Configuration
Based on network 192.168.11.x:
Channel 1 (http://192.168.11.200):
Device IP: 192.168.11.200
Baud Rate: 19200
Subnet Mask: 255.255.255.0
Gateway: 192.168.11.1
Channel 2 (http://192.168.11.201):
Device IP: 192.168.11.201
Baud Rate: 19200
Subnet Mask: 255.255.255.0
Gateway: 192.168.11.1
For Additional Help:
- Waveshare Wiki: https://www.waveshare.com/wiki/2-CH_RS485_TO_ETH_(B)
- Support: Contact us for configuration assistance