Fixing reconnect issues after outage
This commit is contained in:
@@ -0,0 +1,409 @@
|
|||||||
|
# Modbus RTU Monitor Integration - Development Guide
|
||||||
|
|
||||||
|
## Overview
|
||||||
|
|
||||||
|
This integration provides **passive monitoring** of Modbus RTU communication over TCP connections. It listens to existing Modbus traffic between a gateway and slave devices (e.g., thermostats) and creates Home Assistant entities based on discovered data.
|
||||||
|
|
||||||
|
**Key Feature**: Non-intrusive monitoring - the integration does not initiate Modbus requests, it only observes traffic. The exception is the climate entity's setpoint write functionality.
|
||||||
|
|
||||||
|
## Use Case & Background
|
||||||
|
|
||||||
|
This integration was developed to enable remote control and monitoring of proprietary thermostats that are integrated into a complex PLC-based heat automation system via Modbus RTU.
|
||||||
|
|
||||||
|
### Real-World Scenario
|
||||||
|
|
||||||
|
**Current Setup**:
|
||||||
|
- Multiple proprietary thermostats connected via 2 Modbus RTU lines
|
||||||
|
- Complex PLC (Programmable Logic Controller) manages heat automation
|
||||||
|
- PLC writes configuration registers to thermostats (time, mode, pump status)
|
||||||
|
- PLC reads sensor data from thermostats (temperature, humidity, setpoint)
|
||||||
|
|
||||||
|
**Challenges**:
|
||||||
|
- Proprietary thermostats with no native Home Assistant support
|
||||||
|
- Cannot interrupt or interfere with critical PLC communication
|
||||||
|
- Need to read temperature/humidity and set setpoint remotely
|
||||||
|
- Existing automation must continue functioning during transition
|
||||||
|
|
||||||
|
**Solution Approach**:
|
||||||
|
- **Passive monitoring**: Observe PLC ↔ thermostat communication without disruption
|
||||||
|
- **Selective writes**: Only write setpoint when user changes it in HA
|
||||||
|
- **Gradual migration path**: Enables Home Assistant integration while PLC continues operating
|
||||||
|
- **Future goal**: Eventually replace PLC entirely with Home Assistant automations
|
||||||
|
|
||||||
|
### Why Passive Monitoring Matters
|
||||||
|
|
||||||
|
The PLC continuously communicates with thermostats to:
|
||||||
|
- Synchronize time (hour/minute registers)
|
||||||
|
- Set operating modes (summer/winter mode)
|
||||||
|
- Control heat pump status (zone pump register 211)
|
||||||
|
- Read temperature, humidity, and manual mode setpoint
|
||||||
|
|
||||||
|
**Critical**: Any polling or active queries from Home Assistant could:
|
||||||
|
- Disrupt time-sensitive PLC communication
|
||||||
|
- Cause Modbus bus contention
|
||||||
|
- Potentially confuse the PLC or thermostats
|
||||||
|
- Create unpredictable heating behavior
|
||||||
|
|
||||||
|
**Passive monitoring solves this** by only observing existing traffic, making the integration completely invisible to the PLC and thermostats (except for explicit setpoint writes initiated by users).
|
||||||
|
|
||||||
|
### Migration Strategy
|
||||||
|
|
||||||
|
1. **Phase 1** (Current): Passive monitoring + manual setpoint control
|
||||||
|
- Read all sensor data (temp, humidity, registers)
|
||||||
|
- Allow manual temperature adjustment from HA
|
||||||
|
- PLC continues all automation logic
|
||||||
|
|
||||||
|
2. **Phase 2** (Future): Gradual automation takeover
|
||||||
|
- Start replacing PLC automations with HA automations
|
||||||
|
- Monitor additional registers to understand PLC logic
|
||||||
|
- Test HA automations alongside PLC
|
||||||
|
|
||||||
|
3. **Phase 3** (Goal): Full HA control
|
||||||
|
- HA handles all heating automation
|
||||||
|
- PLC decommissioned or relegated to backup role
|
||||||
|
- Complete integration with HA ecosystem
|
||||||
|
|
||||||
|
This integration is the foundation for this migration path.
|
||||||
|
|
||||||
|
## Architecture
|
||||||
|
|
||||||
|
### Core Components
|
||||||
|
|
||||||
|
1. **hub.py** - Central communication hub
|
||||||
|
- Manages TCP connection to Modbus gateway
|
||||||
|
- Passively decodes Modbus RTU frames
|
||||||
|
- Handles reconnection logic for extended outages
|
||||||
|
- Provides active write capability for setpoint changes
|
||||||
|
|
||||||
|
2. **coordinator.py** - Data update coordinator
|
||||||
|
- Manages entity updates efficiently
|
||||||
|
- Uses throttled updates (5-second minimum interval)
|
||||||
|
- Coordinates between hub and entity platforms
|
||||||
|
|
||||||
|
3. **Entity Platforms**:
|
||||||
|
- **climate.py** - Thermostat control with HVAC action display
|
||||||
|
- **sensor.py** - Humidity and register monitoring
|
||||||
|
- **binary_sensor.py** - Coil states and zone pump status
|
||||||
|
|
||||||
|
4. **const.py** - Constants and data models
|
||||||
|
- Register addresses and ranges
|
||||||
|
- SlaveData and ModbusRTUFrame dataclasses
|
||||||
|
- User-friendly register name mappings
|
||||||
|
|
||||||
|
## Critical Implementation Details
|
||||||
|
|
||||||
|
### Reconnection Logic (CRITICAL)
|
||||||
|
|
||||||
|
The integration must handle extended server outages (1-4+ hours) gracefully:
|
||||||
|
|
||||||
|
**Key Requirements**:
|
||||||
|
1. **Monitor task is always created** - even if initial connection fails (hub.py lines 198-220)
|
||||||
|
2. Always null `_reader` and `_writer` after failed reconnection attempts
|
||||||
|
3. Check `if self._reader is None:` before attempting to read
|
||||||
|
4. Exception handler must detect connection errors and trigger reconnection
|
||||||
|
5. Buffer must be cleared after reconnection attempts
|
||||||
|
6. Reconnection delay is 30 seconds (prevents DDOS during outages)
|
||||||
|
|
||||||
|
**Files**: hub.py lines 198-333
|
||||||
|
|
||||||
|
**Why This Matters**:
|
||||||
|
- Without the monitor task being always created, integrations loaded while server is down never attempt reconnection
|
||||||
|
- Without proper state management, the integration enters an infinite error loop after the first failed reconnection
|
||||||
|
- Both scenarios require manual reload without these fixes
|
||||||
|
|
||||||
|
**Critical Design Decision**:
|
||||||
|
- The monitor task handles ALL connection logic (hub.py:254-285)
|
||||||
|
- `async_setup()` only creates tasks, never attempts connection directly (hub.py:198-212)
|
||||||
|
- This prevents race conditions between setup and reconnection logic
|
||||||
|
- First connection attempt is immediate (no delay)
|
||||||
|
- Subsequent reconnection attempts use 30-second delay to prevent DDOS
|
||||||
|
|
||||||
|
### Passive Monitoring Pattern
|
||||||
|
|
||||||
|
The integration monitors three types of Modbus traffic:
|
||||||
|
|
||||||
|
1. **Temperature/Humidity** (Register 0x83, 4 registers)
|
||||||
|
- Detected when request matches TEMP_HUMIDITY_REGISTER
|
||||||
|
- Response contains temperature (index 2) and humidity (index 3)
|
||||||
|
- Values divided by 10 for actual reading
|
||||||
|
|
||||||
|
2. **Coils** (Function code 0x01, 40 coils starting at address 1)
|
||||||
|
- Binary states (ON/OFF)
|
||||||
|
- Disabled by default (user can enable)
|
||||||
|
|
||||||
|
3. **Register Ranges** (Function code 0x03):
|
||||||
|
- Range 1: 165-184 (20 registers) - REGISTER_START_ADDRESS
|
||||||
|
- Range 2: 210-217 (8 registers) - REGISTER_START_ADDRESS_2
|
||||||
|
- Range 3: 140-162 (23 registers) - REGISTER_START_ADDRESS_3
|
||||||
|
|
||||||
|
**Pattern**: Hub detects request frames, stores pending request data, then matches response frames to extract values.
|
||||||
|
|
||||||
|
### Register Name Mapping
|
||||||
|
|
||||||
|
User-friendly names are maintained in `const.py` REGISTER_NAMES dictionary:
|
||||||
|
|
||||||
|
```python
|
||||||
|
REGISTER_NAMES: dict[int, str] = {
|
||||||
|
144: "Setpoint", # Target temperature (written by PLC or HA)
|
||||||
|
145: "Max Setpoint", # Maximum allowed temperature
|
||||||
|
146: "Min Setpoint", # Minimum allowed temperature
|
||||||
|
154: "Hour", # Current hour (synchronized by PLC)
|
||||||
|
155: "Minute", # Current minute (synchronized by PLC)
|
||||||
|
156: "Day of week", # Current day (synchronized by PLC)
|
||||||
|
157: "Current temperature", # Actual temperature reading
|
||||||
|
179: "Outside temperature", # External temperature sensor
|
||||||
|
211: "Zone pump", # Heat pump/zone valve status (1=ON, 0=OFF)
|
||||||
|
}
|
||||||
|
```
|
||||||
|
|
||||||
|
**PLC-Written Registers**: The PLC writes registers 154-156 (time sync) and 211 (pump control). These are monitored to understand system state but should not be written by HA while the PLC is active.
|
||||||
|
|
||||||
|
**HA-Writable Register**: Register 144 (Setpoint) can be safely written by Home Assistant when users adjust temperature, as this mimics manual thermostat adjustment.
|
||||||
|
|
||||||
|
**To add new mappings**: Update REGISTER_NAMES in const.py - sensor entities will automatically use friendly names. As you discover more registers through monitoring, document their purpose here.
|
||||||
|
|
||||||
|
### Climate Entity Bidirectional Sync
|
||||||
|
|
||||||
|
The climate entity maintains setpoint synchronization in both directions:
|
||||||
|
|
||||||
|
1. **User sets temperature in HA**:
|
||||||
|
- Climate entity writes to device via hub.async_write_setpoint()
|
||||||
|
- Immediately updates coordinator data to prevent UI flicker
|
||||||
|
- Scaled value (temp × 10) written to register 144
|
||||||
|
|
||||||
|
2. **Physical thermostat changes setpoint**:
|
||||||
|
- Hub passively monitors register 144
|
||||||
|
- Climate entity reads from coordinator.data[slave_id].registers[144]
|
||||||
|
- Scales value (÷ 10) for display
|
||||||
|
|
||||||
|
**Key Detail**: Register 144 value is immediately updated after write to prevent UI from showing stale value until next monitoring cycle.
|
||||||
|
|
||||||
|
### HVAC Action Display
|
||||||
|
|
||||||
|
Climate entity shows heating status based on register 211:
|
||||||
|
- `HVACAction.HEATING` when register 211 = 1
|
||||||
|
- `HVACAction.IDLE` when register 211 = 0 or unavailable
|
||||||
|
|
||||||
|
**Dual Representation**: Register 211 exists as both:
|
||||||
|
- Regular sensor showing raw integer value (disabled by default)
|
||||||
|
- Binary sensor "Zone pump" showing ON/OFF state (enabled by default)
|
||||||
|
|
||||||
|
This allows users to choose their preferred representation.
|
||||||
|
|
||||||
|
### Entity Default States
|
||||||
|
|
||||||
|
- **Enabled by default**: Humidity sensor, zone pump binary sensor, climate entity
|
||||||
|
- **Disabled by default**: All register sensors (except humidity), all coil sensors
|
||||||
|
|
||||||
|
Users can selectively enable the entities they need.
|
||||||
|
|
||||||
|
## Data Flow
|
||||||
|
|
||||||
|
```
|
||||||
|
Modbus Gateway ←→ TCP Connection ←→ Hub (passive monitoring)
|
||||||
|
↓ (frames decoded)
|
||||||
|
discovered_slaves dict
|
||||||
|
↓ (throttled updates)
|
||||||
|
Coordinator
|
||||||
|
↓
|
||||||
|
Entity Platforms (climate, sensor, binary_sensor)
|
||||||
|
```
|
||||||
|
|
||||||
|
### Update Throttling
|
||||||
|
|
||||||
|
**Coordinator Updates**: Minimum 5-second interval between updates
|
||||||
|
- Defined in COORDINATOR_UPDATE_INTERVAL
|
||||||
|
- Prevents overwhelming Home Assistant with high-frequency Modbus traffic
|
||||||
|
- Hub calls `_update_coordinator_throttled()` which checks timing
|
||||||
|
|
||||||
|
**Why**: Modbus traffic can be very frequent (multiple times per second). Without throttling, HA UI becomes sluggish.
|
||||||
|
|
||||||
|
## Connection Handling
|
||||||
|
|
||||||
|
### Multiple Servers
|
||||||
|
|
||||||
|
Users can configure multiple Modbus gateways as separate config entries. Each entry creates its own:
|
||||||
|
- Hub instance with dedicated TCP connection
|
||||||
|
- Monitor task
|
||||||
|
- Set of discovered slaves and entities
|
||||||
|
|
||||||
|
**Important**: 30-second reconnection delay prevents DDOS when multiple servers are offline simultaneously.
|
||||||
|
|
||||||
|
### Availability Tracking
|
||||||
|
|
||||||
|
Slaves are marked unavailable if no data received for 5 minutes (AVAILABILITY_TIMEOUT).
|
||||||
|
|
||||||
|
**Implementation**: Separate `_availability_check_loop()` runs every 60 seconds and compares `last_seen` timestamp.
|
||||||
|
|
||||||
|
## Modbus Protocol Details
|
||||||
|
|
||||||
|
### RTU Frame Structure
|
||||||
|
|
||||||
|
```
|
||||||
|
[Slave ID][Function Code][Data...][CRC Low][CRC High]
|
||||||
|
```
|
||||||
|
|
||||||
|
**CRC Calculation**: Uses Modbus RTU CRC-16 algorithm (polynomial 0xA001)
|
||||||
|
|
||||||
|
### Supported Function Codes
|
||||||
|
|
||||||
|
- **0x01**: Read Coils (request + response with bitmap)
|
||||||
|
- **0x03**: Read Holding Registers (request + response with values)
|
||||||
|
- **0x06**: Write Single Register (used for setpoint writes)
|
||||||
|
|
||||||
|
### Signed vs Unsigned Integers
|
||||||
|
|
||||||
|
Modbus uses unsigned 16-bit values, but physical readings can be negative (e.g., temperatures).
|
||||||
|
|
||||||
|
**Conversion** (hub.py):
|
||||||
|
```python
|
||||||
|
if value > 32767:
|
||||||
|
signed_value = value - 65536
|
||||||
|
else:
|
||||||
|
signed_value = value
|
||||||
|
```
|
||||||
|
|
||||||
|
This converts unsigned to signed int16 representation.
|
||||||
|
|
||||||
|
## Common Development Tasks
|
||||||
|
|
||||||
|
### Adding New Register Mappings
|
||||||
|
|
||||||
|
1. Identify register address and purpose through monitoring
|
||||||
|
2. Update `REGISTER_NAMES` in const.py:
|
||||||
|
```python
|
||||||
|
REGISTER_NAMES: dict[int, str] = {
|
||||||
|
# ... existing mappings ...
|
||||||
|
XXX: "Your Register Name",
|
||||||
|
}
|
||||||
|
```
|
||||||
|
3. Sensors automatically display friendly name
|
||||||
|
|
||||||
|
### Extending Monitored Register Ranges
|
||||||
|
|
||||||
|
To monitor additional register ranges:
|
||||||
|
|
||||||
|
1. Add constants to const.py:
|
||||||
|
```python
|
||||||
|
REGISTER_START_ADDRESS_4 = 0xYY # Your start address
|
||||||
|
REGISTER_MONITOR_COUNT_4 = ZZ # Number of registers
|
||||||
|
```
|
||||||
|
|
||||||
|
2. Update hub.py `_handle_frame()` to detect requests/responses for the new range
|
||||||
|
- Follow pattern from existing ranges (1, 2, 3)
|
||||||
|
- Use unique pending request key (e.g., `f"{slave_id}_registers4"`)
|
||||||
|
|
||||||
|
3. Update sensor.py `async_setup_entry()` to create sensors for new range
|
||||||
|
- Add tracking set (e.g., `added_slaves_registers4`)
|
||||||
|
- Add sensor creation logic in `_async_add_sensor_entities()`
|
||||||
|
|
||||||
|
### Testing Reconnection Logic
|
||||||
|
|
||||||
|
**Critical Test**: Long outage scenario
|
||||||
|
```bash
|
||||||
|
# 1. Start integration with working server
|
||||||
|
# 2. Stop Modbus server
|
||||||
|
# 3. Wait 2+ hours
|
||||||
|
# 4. Check logs - should see reconnection attempts every ~30 seconds
|
||||||
|
# 5. Start Modbus server
|
||||||
|
# 6. Verify automatic reconnection within 30 seconds
|
||||||
|
# 7. Verify data flow resumes without manual reload
|
||||||
|
```
|
||||||
|
|
||||||
|
## Known Issues and Solutions
|
||||||
|
|
||||||
|
### Issue: UI Flicker When Setting Temperature
|
||||||
|
|
||||||
|
**Symptom**: After setting temperature, UI briefly reverts to old value before updating.
|
||||||
|
|
||||||
|
**Solution**: Immediately update `slave_data.registers[SETPOINT_REGISTER]` after successful write (climate.py line 178).
|
||||||
|
|
||||||
|
### Issue: Integration Won't Reconnect After Long Outage
|
||||||
|
|
||||||
|
**Symptom**: After server outage >1 hour, integration requires manual reload.
|
||||||
|
|
||||||
|
**Root Cause**: Reader/writer not properly nulled on failed reconnection.
|
||||||
|
|
||||||
|
**Solution**: Implemented in hub.py lines 222-333 (see Reconnection Logic section above).
|
||||||
|
|
||||||
|
### Issue: Too Many Connection Attempts During Outage
|
||||||
|
|
||||||
|
**Symptom**: Server logs show connection spam when offline.
|
||||||
|
|
||||||
|
**Solution**: 30-second reconnection delay (hub.py line 237).
|
||||||
|
|
||||||
|
## Code Patterns and Conventions
|
||||||
|
|
||||||
|
### Async Safety
|
||||||
|
|
||||||
|
- All I/O operations are async
|
||||||
|
- Write operations use `self._write_lock` to prevent concurrent access
|
||||||
|
- Coordinator updates use `@callback` decorator where appropriate
|
||||||
|
|
||||||
|
### Logging
|
||||||
|
|
||||||
|
- Debug level: Frame processing details, non-critical events
|
||||||
|
- Info level: Connection status, slave discovery, successful operations
|
||||||
|
- Warning level: Connection loss, reconnection attempts
|
||||||
|
- Error level: Failed reconnections, unexpected errors
|
||||||
|
|
||||||
|
**Format**: Always include `self.host:self.port` in connection-related messages.
|
||||||
|
|
||||||
|
### Entity Registration
|
||||||
|
|
||||||
|
Entities are dynamically created when slaves are discovered:
|
||||||
|
- Use tracking sets (e.g., `added_slaves`, `added_slaves_registers`)
|
||||||
|
- Subscribe to coordinator updates via `async_add_listener()`
|
||||||
|
- Only create entities when new slaves/data detected
|
||||||
|
|
||||||
|
### Device Info
|
||||||
|
|
||||||
|
All entities for a slave share the same device:
|
||||||
|
```python
|
||||||
|
DeviceInfo(
|
||||||
|
identifiers={(DOMAIN, f"{coordinator.config_entry.entry_id}_{slave_id}")},
|
||||||
|
name=f"Modbus Slave {slave_id}",
|
||||||
|
manufacturer=MANUFACTURER,
|
||||||
|
model=MODEL,
|
||||||
|
)
|
||||||
|
```
|
||||||
|
|
||||||
|
## Configuration
|
||||||
|
|
||||||
|
**No YAML configuration** - integration uses config flow only.
|
||||||
|
|
||||||
|
**Config Entry Data**:
|
||||||
|
- `host`: Modbus gateway IP/hostname
|
||||||
|
- `port`: TCP port (default 502)
|
||||||
|
|
||||||
|
**Runtime Data**: Hub instance stored in `entry.runtime_data`
|
||||||
|
|
||||||
|
## Files Overview
|
||||||
|
|
||||||
|
- **manifest.json** - Integration metadata and dependencies
|
||||||
|
- **const.py** - Constants, register addresses, data models
|
||||||
|
- **hub.py** - TCP connection, frame decoding, reconnection logic
|
||||||
|
- **coordinator.py** - Data update coordination
|
||||||
|
- **config_flow.py** - UI configuration
|
||||||
|
- **climate.py** - Thermostat entity
|
||||||
|
- **sensor.py** - Humidity and register sensors
|
||||||
|
- **binary_sensor.py** - Coil and zone pump sensors
|
||||||
|
- **__init__.py** - Integration setup/unload
|
||||||
|
|
||||||
|
## Important Notes for AI Assistants
|
||||||
|
|
||||||
|
1. **Never remove the 30-second reconnection delay** - it prevents DDOS during outages
|
||||||
|
2. **Always clear buffer after reconnection** - prevents processing stale frames
|
||||||
|
3. **Maintain throttling** - Modbus traffic is high-frequency, HA needs protection
|
||||||
|
4. **Preserve passive monitoring** - don't add active polling unless specifically requested
|
||||||
|
5. **Keep register sensors disabled by default** - there are many, most users don't need them
|
||||||
|
6. **Test with extended outages** - this is the most common production issue
|
||||||
|
|
||||||
|
## Future Enhancements
|
||||||
|
|
||||||
|
Potential improvements to consider:
|
||||||
|
- Support for Modbus RTU over serial (currently TCP only)
|
||||||
|
- Configurable register ranges via UI
|
||||||
|
- Entity auto-discovery based on register schema files
|
||||||
|
- Diagnostic sensors for connection statistics
|
||||||
|
- Service to manually trigger reconnection
|
||||||
@@ -197,17 +197,19 @@ class ModbusRTUMonitorHub:
|
|||||||
|
|
||||||
async def async_setup(self) -> bool:
|
async def async_setup(self) -> bool:
|
||||||
"""Set up the hub and start monitoring."""
|
"""Set up the hub and start monitoring."""
|
||||||
try:
|
# Start monitor and availability tasks
|
||||||
await self._connect()
|
# The monitor loop handles all connection logic (initial and reconnections)
|
||||||
self._monitor_task = asyncio.create_task(self._monitor_loop())
|
self._monitor_task = asyncio.create_task(self._monitor_loop())
|
||||||
self._availability_task = asyncio.create_task(
|
self._availability_task = asyncio.create_task(
|
||||||
self._availability_check_loop()
|
self._availability_check_loop()
|
||||||
)
|
)
|
||||||
return True
|
|
||||||
except Exception as ex:
|
_LOGGER.info(
|
||||||
raise ConfigEntryNotReady(
|
"Modbus RTU Monitor hub starting for %s:%s (monitor task will establish connection)",
|
||||||
f"Failed to connect to {self.host}:{self.port}"
|
self.host,
|
||||||
) from ex
|
self.port,
|
||||||
|
)
|
||||||
|
return True
|
||||||
|
|
||||||
async def _connect(self) -> None:
|
async def _connect(self) -> None:
|
||||||
"""Establish TCP connection."""
|
"""Establish TCP connection."""
|
||||||
@@ -252,15 +254,36 @@ class ModbusRTUMonitorHub:
|
|||||||
async def _monitor_loop(self) -> None:
|
async def _monitor_loop(self) -> None:
|
||||||
"""Main monitoring loop for passive frame reception."""
|
"""Main monitoring loop for passive frame reception."""
|
||||||
buffer = bytearray()
|
buffer = bytearray()
|
||||||
|
first_connection_attempt = True
|
||||||
|
consecutive_timeouts = 0
|
||||||
|
TIMEOUT_THRESHOLD = 30 # 30 timeouts = 30 seconds of no data
|
||||||
|
|
||||||
while True:
|
while True:
|
||||||
try:
|
try:
|
||||||
# Check if reader is valid before attempting to read
|
# Check if reader is valid before attempting to read
|
||||||
if self._reader is None:
|
if self._reader is None:
|
||||||
# No active connection, attempt reconnect
|
consecutive_timeouts = 0 # Reset counter after reconnect attempt
|
||||||
_LOGGER.info("No active connection to %s:%s, attempting reconnect", self.host, self.port)
|
if first_connection_attempt:
|
||||||
await self._reconnect()
|
# First connection attempt - try immediately without delay
|
||||||
# Clear buffer for fresh start after reconnection
|
_LOGGER.info("Attempting initial connection to %s:%s", self.host, self.port)
|
||||||
|
first_connection_attempt = False
|
||||||
|
try:
|
||||||
|
await self._connect()
|
||||||
|
_LOGGER.info("Connected to Modbus gateway at %s:%s", self.host, self.port)
|
||||||
|
except Exception as ex:
|
||||||
|
_LOGGER.warning(
|
||||||
|
"Initial connection failed to %s:%s - %s (will retry)",
|
||||||
|
self.host,
|
||||||
|
self.port,
|
||||||
|
ex,
|
||||||
|
)
|
||||||
|
# Fall through to reconnect logic with delay
|
||||||
|
await asyncio.sleep(30)
|
||||||
|
else:
|
||||||
|
# Subsequent reconnection attempts - use delay to prevent DDOS
|
||||||
|
_LOGGER.info("No active connection to %s:%s, attempting reconnect", self.host, self.port)
|
||||||
|
await self._reconnect()
|
||||||
|
# Clear buffer for fresh start after connection attempt
|
||||||
buffer.clear()
|
buffer.clear()
|
||||||
continue
|
continue
|
||||||
|
|
||||||
@@ -268,13 +291,17 @@ class ModbusRTUMonitorHub:
|
|||||||
data = await asyncio.wait_for(self._reader.read(1024), timeout=1.0)
|
data = await asyncio.wait_for(self._reader.read(1024), timeout=1.0)
|
||||||
|
|
||||||
if not data:
|
if not data:
|
||||||
# Connection closed
|
# Connection closed gracefully
|
||||||
_LOGGER.warning("Connection closed to %s:%s, attempting reconnect", self.host, self.port)
|
_LOGGER.warning("Connection closed to %s:%s, attempting reconnect", self.host, self.port)
|
||||||
|
consecutive_timeouts = 0 # Reset counter
|
||||||
await self._reconnect()
|
await self._reconnect()
|
||||||
# Clear buffer for fresh start after reconnection
|
# Clear buffer for fresh start after reconnection
|
||||||
buffer.clear()
|
buffer.clear()
|
||||||
continue
|
continue
|
||||||
|
|
||||||
|
# Successfully received data - reset timeout counter
|
||||||
|
consecutive_timeouts = 0
|
||||||
|
|
||||||
buffer.extend(data)
|
buffer.extend(data)
|
||||||
|
|
||||||
# Process frames from buffer (limit iterations to prevent blocking)
|
# Process frames from buffer (limit iterations to prevent blocking)
|
||||||
@@ -309,7 +336,26 @@ class ModbusRTUMonitorHub:
|
|||||||
await asyncio.sleep(FRAME_PROCESSING_DELAY)
|
await asyncio.sleep(FRAME_PROCESSING_DELAY)
|
||||||
|
|
||||||
except asyncio.TimeoutError:
|
except asyncio.TimeoutError:
|
||||||
# Normal timeout, continue
|
# Track consecutive timeouts to detect dead connections
|
||||||
|
consecutive_timeouts += 1
|
||||||
|
|
||||||
|
if consecutive_timeouts >= TIMEOUT_THRESHOLD:
|
||||||
|
# Connection appears dead (30+ seconds of no data)
|
||||||
|
_LOGGER.warning(
|
||||||
|
"Connection timeout to %s:%s (%d consecutive timeouts, %ds with no data) - assuming connection dead, will reconnect",
|
||||||
|
self.host,
|
||||||
|
self.port,
|
||||||
|
consecutive_timeouts,
|
||||||
|
consecutive_timeouts,
|
||||||
|
)
|
||||||
|
# Null reader/writer to trigger reconnection on next iteration
|
||||||
|
self._reader = None
|
||||||
|
self._writer = None
|
||||||
|
consecutive_timeouts = 0
|
||||||
|
# Clear buffer for fresh start
|
||||||
|
buffer.clear()
|
||||||
|
|
||||||
|
# Continue to next iteration (either to reconnect or wait for next timeout)
|
||||||
continue
|
continue
|
||||||
except asyncio.CancelledError:
|
except asyncio.CancelledError:
|
||||||
break
|
break
|
||||||
@@ -324,12 +370,14 @@ class ModbusRTUMonitorHub:
|
|||||||
# Null out connection and trigger reconnect
|
# Null out connection and trigger reconnect
|
||||||
self._reader = None
|
self._reader = None
|
||||||
self._writer = None
|
self._writer = None
|
||||||
|
consecutive_timeouts = 0 # Reset counter
|
||||||
await self._reconnect()
|
await self._reconnect()
|
||||||
buffer.clear()
|
buffer.clear()
|
||||||
continue
|
continue
|
||||||
except Exception as ex:
|
except Exception as ex:
|
||||||
# Other unexpected errors
|
# Other unexpected errors
|
||||||
_LOGGER.error("Unexpected error in monitor loop for %s:%s - %s", self.host, self.port, ex)
|
_LOGGER.error("Unexpected error in monitor loop for %s:%s - %s", self.host, self.port, ex)
|
||||||
|
consecutive_timeouts = 0 # Reset counter on unexpected errors
|
||||||
await asyncio.sleep(5)
|
await asyncio.sleep(5)
|
||||||
|
|
||||||
async def _handle_frame(self, frame: ModbusRTUFrame) -> None:
|
async def _handle_frame(self, frame: ModbusRTUFrame) -> None:
|
||||||
|
|||||||