# CLAUDE.md - Development Context for Excess PV Boiler Control
|
||||||
|
|
||||||
|
## Project Purpose
|
||||||
|
|
||||||
|
This Home Assistant package controls an auxiliary electric heater installed in a DHW (Domestic Hot Water) boiler. It works alongside a heat pump to provide:
|
||||||
|
- **Preset-based temperature control** with user-adjustable temperatures per preset
|
||||||
|
- **PV excess utilization** to use surplus solar power instead of exporting
|
||||||
|
- **Bath boost** with configurable timer for rapid hot water
|
||||||
|
- **Manual override** for emergency/testing scenarios
|
||||||
|
|
||||||
|
## Architecture
|
||||||
|
|
||||||
|
```
|
||||||
|
[Solar Inverter] --> sensor.deye_12_external_ct*_power (3-phase grid power)
|
||||||
|
|
|
||||||
|
[binary_sensor.dhw_pv_power_enough_for_aux_heater]
|
||||||
|
|
|
||||||
|
[automation: DHW Manage PV Thermostat]
|
||||||
|
|
|
||||||
|
[climate.dhw_pv_excess_heating] (shadow thermostat)
|
||||||
|
|
|
||||||
|
[binary_sensor.dhw_use_boiler_aux_heater] <-- [manual override]
|
||||||
|
| <-- [boost modes]
|
||||||
|
[automation: DHW Boiler Heater Relay]
|
||||||
|
|
|
||||||
|
[switch.boiler_heater_relay_switch_0] (physical relay)
|
||||||
|
|
||||||
|
[input_select.dhw_boiler_preset] --> [automation: DHW Boiler Preset Manager]
|
||||||
|
[input_number.dhw_boiler_temp_*] |
|
||||||
|
v
|
||||||
|
[climate.boiler_temperature] (main thermostat)
|
||||||
|
|
||||||
|
[script.dhw_start_bath_boost] --> [timer.bath_time] --> [automation: DHW Bath Time]
|
||||||
|
[input_number.dhw_bath_boost_duration] |
|
||||||
|
v
|
||||||
|
[input_boolean.dhw_bath_boost] + [switch.acm_pump_switch]
|
||||||
|
```
|
||||||
|
|
||||||
|
## Key Entities
|
||||||
|
|
||||||
|
### Input Booleans (Modes/Toggles)
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `input_boolean.dhw_aux_heater_manual_override` | Force heater ON regardless of conditions |
|
||||||
|
| `input_boolean.dhw_allow_aux_heater_usage` | Master enable for aux heater |
|
||||||
|
| `input_boolean.dhw_use_excess_pv_for_aux_heater` | Enable PV excess mode |
|
||||||
|
| `input_boolean.dhw_allow_aux_heater_in_all_modes` | Allow boost in normal thermostat mode |
|
||||||
|
| `input_boolean.boiler_pv_dummy_heater` | Virtual switch for shadow thermostat |
|
||||||
|
| `input_boolean.dhw_bath_boost` | Bath boost active flag (managed by automations) |
|
||||||
|
|
||||||
|
### Input Select (Presets)
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `input_select.dhw_boiler_preset` | Active boiler preset: Normal, Eco, Boost, Sleep, Away, Off |
|
||||||
|
|
||||||
|
### Timer
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `timer.bath_time` | Countdown timer for bath boost duration |
|
||||||
|
|
||||||
|
### Input Numbers (Thresholds)
|
||||||
|
| Entity | Purpose | Range |
|
||||||
|
|--------|---------|-------|
|
||||||
|
| `input_number.dhw_aux_heater_cut_off_temperature_threshold` | Max temp before heater stops | 50-85°C |
|
||||||
|
| `input_number.dhw_aux_heater_temperature_threshold` | Hysteresis threshold | 1-15°C |
|
||||||
|
| `input_number.dhw_pv_target_temperature` | Target temp for PV heating | 40-70°C |
|
||||||
|
| `input_number.dhw_pv_excess_usage_buffer` | Buffer power before triggering | 0-1000W |
|
||||||
|
| `input_number.dhw_aux_heater_power` | Heater power rating | 500-9000W |
|
||||||
|
| `input_number.dhw_pv_excess_usage_start_delay` | Delay before starting PV mode | 1-300s |
|
||||||
|
| `input_number.dhw_pv_excess_usage_stop_delay` | Delay before stopping PV mode | 1-300s |
|
||||||
|
|
||||||
|
### Input Numbers (Preset Temperatures)
|
||||||
|
| Entity | Purpose | Range |
|
||||||
|
|--------|---------|-------|
|
||||||
|
| `input_number.dhw_boiler_temp_normal` | Normal preset target temperature | 30-65°C |
|
||||||
|
| `input_number.dhw_boiler_temp_eco` | Eco preset target temperature | 30-60°C |
|
||||||
|
| `input_number.dhw_boiler_temp_boost` | Boost preset target temperature | 40-70°C |
|
||||||
|
| `input_number.dhw_boiler_temp_sleep` | Sleep preset target temperature | 25-55°C |
|
||||||
|
| `input_number.dhw_boiler_temp_away` | Away preset target temperature | 20-50°C |
|
||||||
|
| `input_number.dhw_bath_boost_duration` | Duration for bath boost timer | 5-120 min |
|
||||||
|
|
||||||
|
### Scripts
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `script.dhw_start_bath_boost` | Starts `timer.bath_time` with duration from `dhw_bath_boost_duration` |
|
||||||
|
|
||||||
|
### Climate (Generic Thermostats)
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `climate.dhw_pv_excess_heating` | Shadow thermostat for PV excess mode |
|
||||||
|
| `climate.boiler_temperature` | Main boiler thermostat (target set by preset manager) |
|
||||||
|
|
||||||
|
### Automations
|
||||||
|
| Entity | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `DHW Boiler Heater Relay Automation` | Switches physical relay based on decision sensor |
|
||||||
|
| `DHW Manage PV Thermostat` | Controls shadow thermostat based on PV availability |
|
||||||
|
| `DHW Boiler Preset Manager` | Syncs preset selection + temperatures to thermostat, toggles bath boost |
|
||||||
|
| `DHW Bath Time` | Manages bath boost lifecycle: pump + boost on/off with timer |
|
||||||
|
|
||||||
|
### External Entities (Not Defined in Package)
|
||||||
|
These must exist in your HA instance from other integrations or manual UI setup:
|
||||||
|
|
||||||
|
| Entity | Source | Purpose | Fallback if Unavailable |
|
||||||
|
|--------|--------|---------|------------------------|
|
||||||
|
| `sensor.boiler_temp` | Heat pump / temperature probe | Boiler water temperature | 100 (prevents running) |
|
||||||
|
| `sensor.deye_12_external_ct1_power` | Deye inverter integration | Phase 1 grid power (negative = export) | 0 |
|
||||||
|
| `sensor.deye_12_external_ct2_power` | Deye inverter integration | Phase 2 grid power | 0 |
|
||||||
|
| `sensor.deye_12_external_ct3_power` | Deye inverter integration | Phase 3 grid power | 0 |
|
||||||
|
| `sensor.heat_pump_auxiliary_heater` | Heat pump integration | HP aux heater state | treated as 'off' |
|
||||||
|
| `switch.boiler_heater_relay_switch_0` | Relay device (Shelly, etc.) | Physical heater control | N/A |
|
||||||
|
| `switch.acm_pump_switch` | Pump relay/smart plug | DHW circulation pump | N/A |
|
||||||
|
| `switch.schedule_f403a3` | Scheduler integration | Pump schedule to restore after boost | N/A |
|
||||||
|
|
||||||
|
## Decision Logic
|
||||||
|
|
||||||
|
### binary_sensor.dhw_use_boiler_aux_heater
|
||||||
|
This is the main decision sensor. It turns ON when:
|
||||||
|
1. **Manual override** is ON, OR
|
||||||
|
2. **All conditions met**:
|
||||||
|
- Heat pump aux heater is OFF
|
||||||
|
- Boiler aux usage is allowed
|
||||||
|
- Boiler temp is below cut-off threshold
|
||||||
|
- AND one of:
|
||||||
|
- PV excess mode active AND shadow thermostat is heating
|
||||||
|
- Bath boost active AND main thermostat is heating
|
||||||
|
- All-modes boost enabled AND main thermostat is heating
|
||||||
|
|
||||||
|
### binary_sensor.dhw_pv_power_enough_for_aux_heater
|
||||||
|
Determines if there's enough solar export to run the heater:
|
||||||
|
- **When heater is OFF**: All 3 phases must export > (buffer + heater_power) / 3
|
||||||
|
- **When heater is ON**: All 3 phases must still be exporting (<=0W import)
|
||||||
|
|
||||||
|
### Preset Manager Flow
|
||||||
|
1. User selects preset from `input_select.dhw_boiler_preset`
|
||||||
|
2. Automation reads corresponding `input_number.dhw_boiler_temp_<preset>` value
|
||||||
|
3. Sets `climate.boiler_temperature` to that target + heat mode (or off for "Off" preset)
|
||||||
|
4. Toggles `input_boolean.dhw_bath_boost` on/off based on whether Boost is selected
|
||||||
|
5. If user changes a preset temperature input_number, automation re-applies current preset
|
||||||
|
|
||||||
|
### Bath Boost Flow
|
||||||
|
1. User calls `script.dhw_start_bath_boost` (e.g., from a dashboard button)
|
||||||
|
2. Script starts `timer.bath_time` with duration from `input_number.dhw_bath_boost_duration`
|
||||||
|
3. `DHW Bath Time` automation detects timer active: turns on pump + bath boost
|
||||||
|
4. Timer finishes: automation restores pump schedule + turns off boost
|
||||||
|
|
||||||
|
## Common Modifications
|
||||||
|
|
||||||
|
### Changing Preset Temperatures
|
||||||
|
Adjust via dashboard sliders at runtime (no YAML edit needed).
|
||||||
|
The `input_number.dhw_boiler_temp_*` entities store each preset's temperature.
|
||||||
|
|
||||||
|
### Adding New Presets
|
||||||
|
1. Add option to `input_select.dhw_boiler_preset`
|
||||||
|
2. Add corresponding `input_number.dhw_boiler_temp_<name>` (name must be lowercase match)
|
||||||
|
3. The preset manager automation uses dynamic entity resolution, so no automation changes needed
|
||||||
|
|
||||||
|
### Changing Power Thresholds
|
||||||
|
Adjust via dashboard at runtime:
|
||||||
|
- `dhw_pv_excess_usage_buffer`: Increase for more conservative PV triggering
|
||||||
|
- `dhw_aux_heater_power`: Match to actual heater rating
|
||||||
|
|
||||||
|
### Adjusting Timing
|
||||||
|
Adjust via dashboard at runtime:
|
||||||
|
- `dhw_pv_excess_usage_start_delay`: Increase to avoid rapid cycling
|
||||||
|
- `dhw_pv_excess_usage_stop_delay`: Increase to ride through clouds
|
||||||
|
- `dhw_bath_boost_duration`: Duration of bath boost timer
|
||||||
|
|
||||||
|
### Adding New Heating Modes
|
||||||
|
Edit template section, add new condition in `binary_sensor.dhw_use_boiler_aux_heater` alongside `pv_excess`, `thermostat_activity_boost`, etc.
|
||||||
|
|
||||||
|
## Testing/Validation
|
||||||
|
|
||||||
|
1. **YAML Syntax**: Run `yamllint *.yaml` or use HA's configuration check
|
||||||
|
2. **Entity References**: Ensure all `states()` calls reference defined entities
|
||||||
|
3. **Default Fallbacks**: Verify all `float()` filters have appropriate defaults:
|
||||||
|
- Temperature sensors: `float(100)` (fail-safe: heater OFF)
|
||||||
|
- Power sensors: `float(0)` (fail-safe: no export detected)
|
||||||
|
- Input numbers: `float(<sensible_default>)`
|
||||||
|
|
||||||
|
## File Structure
|
||||||
|
|
||||||
|
| File | Purpose |
|
||||||
|
|------|---------|
|
||||||
|
| `use_excess_pv_in_boiler.yaml` | **Main package file** - install this in HA packages directory |
|
||||||
|
| `CLAUDE.md` | Development context for AI assistants |
|
||||||
|
| `README.md` | User-facing documentation |
|
||||||
|
|
||||||
|
## Safety Considerations
|
||||||
|
|
||||||
|
1. **Never run both heaters**: Template checks `sensor.heat_pump_auxiliary_heater != 'on'`
|
||||||
|
2. **Temperature cut-off**: Hard limit prevents overheating
|
||||||
|
3. **Unavailable sensors**: Default to safe values (temp=100, power=0)
|
||||||
|
4. **Manual override**: Bypasses all checks - use with caution
|
||||||
|
5. **Bath boost timer**: Auto-disables boost when timer expires
|
||||||
@@ -0,0 +1,258 @@
|
|||||||
|
# Excess PV Boiler Auxiliary Heater Control
|
||||||
|
|
||||||
|
Home Assistant package for controlling an auxiliary electric heater in a DHW (Domestic Hot Water) boiler, designed to work alongside a heat pump system.
|
||||||
|
|
||||||
|
## Features
|
||||||
|
|
||||||
|
- **Preset-based temperature control**: Normal, Eco, Boost, Sleep, Away, Off - with user-adjustable temperatures per preset via dashboard sliders
|
||||||
|
- **PV Excess Utilization**: Automatically uses surplus solar power to heat water instead of exporting to grid
|
||||||
|
- **Bath Boost with Timer**: Timed rapid hot water heating with configurable duration
|
||||||
|
- **Manual Override**: Emergency/testing control
|
||||||
|
- **Safety Interlocks**: Prevents running both heat pump and boiler auxiliary heaters simultaneously
|
||||||
|
- **Energy Tracking**: Runtime and energy consumption stats split by PV vs grid
|
||||||
|
|
||||||
|
## System Architecture
|
||||||
|
|
||||||
|
```
|
||||||
|
SOLAR INVERTER
|
||||||
|
|
|
||||||
|
sensor.deye_12_external_ct1/2/3_power
|
||||||
|
(3-phase grid power monitoring)
|
||||||
|
|
|
||||||
|
v
|
||||||
|
binary_sensor.dhw_pv_power_enough_for_aux_heater
|
||||||
|
Checks: All 3 phases exporting enough?
|
||||||
|
|
|
||||||
|
v
|
||||||
|
automation: DHW Manage PV Thermostat
|
||||||
|
(with configurable start/stop delays)
|
||||||
|
|
|
||||||
|
v
|
||||||
|
climate.dhw_pv_excess_heating
|
||||||
|
(shadow thermostat for PV mode)
|
||||||
|
|
|
||||||
|
v
|
||||||
|
binary_sensor.dhw_use_boiler_aux_heater
|
||||||
|
MAIN DECISION: manual OR (allowed AND
|
||||||
|
(pv_excess OR bath_boost OR normal_boost))
|
||||||
|
|
|
||||||
|
v
|
||||||
|
automation: DHW Boiler Heater Relay
|
||||||
|
|
|
||||||
|
v
|
||||||
|
switch.boiler_heater_relay_switch_0
|
||||||
|
(PHYSICAL RELAY - heater element)
|
||||||
|
|
||||||
|
|
||||||
|
PRESET SYSTEM BATH BOOST
|
||||||
|
-------------- ----------
|
||||||
|
input_select --> Preset script.dhw_start_bath_boost
|
||||||
|
dhw_boiler_preset Manager |
|
||||||
|
input_number --> | timer.bath_time
|
||||||
|
dhw_boiler_temp_* | |
|
||||||
|
v v
|
||||||
|
climate.boiler_temperature DHW Bath Time automation
|
||||||
|
(main thermostat) (pump + boost on/off)
|
||||||
|
```
|
||||||
|
|
||||||
|
## Installation
|
||||||
|
|
||||||
|
1. Copy `use_excess_pv_in_boiler.yaml` to your Home Assistant `packages` directory
|
||||||
|
2. Enable packages in `configuration.yaml`:
|
||||||
|
```yaml
|
||||||
|
homeassistant:
|
||||||
|
packages: !include_dir_named packages
|
||||||
|
```
|
||||||
|
3. Ensure all external entities exist (see [External Dependencies](#external-dependencies))
|
||||||
|
4. Restart Home Assistant
|
||||||
|
5. Configure preset temperatures and thresholds via the UI
|
||||||
|
|
||||||
|
## External Dependencies
|
||||||
|
|
||||||
|
These entities must already exist in your Home Assistant instance from other integrations or devices. They are **not** created by this package.
|
||||||
|
|
||||||
|
### Sensors (from device integrations)
|
||||||
|
|
||||||
|
| Entity | Source | Purpose |
|
||||||
|
|--------|--------|---------|
|
||||||
|
| `sensor.boiler_temp` | Heat pump / temperature probe | Boiler water temperature |
|
||||||
|
| `sensor.deye_12_external_ct1_power` | Deye inverter integration | Phase 1 grid power (negative = export) |
|
||||||
|
| `sensor.deye_12_external_ct2_power` | Deye inverter integration | Phase 2 grid power |
|
||||||
|
| `sensor.deye_12_external_ct3_power` | Deye inverter integration | Phase 3 grid power |
|
||||||
|
| `sensor.heat_pump_auxiliary_heater` | Heat pump integration | HP aux heater state (interlock) |
|
||||||
|
|
||||||
|
### Switches (from device integrations)
|
||||||
|
|
||||||
|
| Entity | Source | Purpose |
|
||||||
|
|--------|--------|---------|
|
||||||
|
| `switch.boiler_heater_relay_switch_0` | Relay device (Shelly, etc.) | Physical heater control |
|
||||||
|
| `switch.acm_pump_switch` | Pump relay / smart plug | DHW circulation pump (used by bath boost) |
|
||||||
|
|
||||||
|
### Scheduler (optional integration)
|
||||||
|
|
||||||
|
| Entity | Source | Purpose |
|
||||||
|
|--------|--------|---------|
|
||||||
|
| `switch.schedule_f403a3` | Scheduler integration | Pump schedule restored after bath boost ends |
|
||||||
|
|
||||||
|
> **Note**: If you don't use the Scheduler integration, remove the `scheduler.run_action` call from the DHW Bath Time automation.
|
||||||
|
|
||||||
|
## Configuration
|
||||||
|
|
||||||
|
### Boiler Temperature Presets
|
||||||
|
|
||||||
|
The preset system uses an `input_select` for mode selection and `input_number` entities for each preset's temperature. Users can adjust all temperatures from the dashboard without editing YAML.
|
||||||
|
|
||||||
|
| Preset | Entity | Range | Intended Use |
|
||||||
|
|--------|--------|-------|-------------|
|
||||||
|
| **Normal** | `input_number.dhw_boiler_temp_normal` | 30-65°C | Everyday hot water |
|
||||||
|
| **Eco** | `input_number.dhw_boiler_temp_eco` | 30-60°C | Energy saving mode |
|
||||||
|
| **Boost** | `input_number.dhw_boiler_temp_boost` | 40-70°C | Rapid heating (also enables aux heater) |
|
||||||
|
| **Sleep** | `input_number.dhw_boiler_temp_sleep` | 25-55°C | Nighttime lower temperature |
|
||||||
|
| **Away** | `input_number.dhw_boiler_temp_away` | 20-50°C | Away from home |
|
||||||
|
| **Off** | — | — | Turns off the boiler thermostat |
|
||||||
|
|
||||||
|
Selecting **Boost** also enables `input_boolean.dhw_bath_boost`, which allows the auxiliary heater to run (through the decision logic). All other presets disable it.
|
||||||
|
|
||||||
|
### Bath Boost Timer
|
||||||
|
|
||||||
|
| Entity | Purpose | Range |
|
||||||
|
|--------|---------|-------|
|
||||||
|
| `input_number.dhw_bath_boost_duration` | Timer duration | 5-120 min (step: 5) |
|
||||||
|
| `script.dhw_start_bath_boost` | Call to start the boost timer | — |
|
||||||
|
| `timer.bath_time` | Active countdown (shows remaining time) | — |
|
||||||
|
|
||||||
|
**How it works**: Call `script.dhw_start_bath_boost` from a dashboard button. The timer starts, the automation turns on the circulation pump (`switch.acm_pump_switch`) and enables bath boost. When the timer expires, both are turned off and the pump schedule is restored.
|
||||||
|
|
||||||
|
### Mode Toggles
|
||||||
|
|
||||||
|
| Entity | Description |
|
||||||
|
|--------|-------------|
|
||||||
|
| `input_boolean.dhw_aux_heater_manual_override` | Forces heater ON regardless of all other conditions |
|
||||||
|
| `input_boolean.dhw_allow_aux_heater_usage` | Master enable switch. Must be ON for any automatic operation |
|
||||||
|
| `input_boolean.dhw_use_excess_pv_for_aux_heater` | Enables PV excess utilization mode |
|
||||||
|
| `input_boolean.dhw_allow_aux_heater_in_all_modes` | Aux heater runs whenever main thermostat calls for heat (any preset) |
|
||||||
|
|
||||||
|
### PV Excess Thresholds
|
||||||
|
|
||||||
|
| Entity | Description | Range |
|
||||||
|
|--------|-------------|-------|
|
||||||
|
| `input_number.dhw_aux_heater_cut_off_temperature_threshold` | Maximum temperature before heater stops | 50-85°C |
|
||||||
|
| `input_number.dhw_pv_target_temperature` | Target temperature when using PV excess | 40-70°C |
|
||||||
|
| `input_number.dhw_pv_excess_usage_buffer` | Extra export power required as safety margin | 0-1000W |
|
||||||
|
| `input_number.dhw_aux_heater_power` | Rated power of your heater element | 500-9000W |
|
||||||
|
| `input_number.dhw_pv_excess_usage_start_delay` | Seconds of stable export before starting | 1-300s |
|
||||||
|
| `input_number.dhw_pv_excess_usage_stop_delay` | Seconds of insufficient export before stopping | 1-300s |
|
||||||
|
|
||||||
|
## Usage Modes
|
||||||
|
|
||||||
|
### 1. Preset-Based Heating
|
||||||
|
|
||||||
|
Select a preset from `input_select.dhw_boiler_preset`. The thermostat target temperature is set automatically from the corresponding `input_number`. Adjust temperatures anytime via dashboard sliders.
|
||||||
|
|
||||||
|
### 2. PV Excess Mode
|
||||||
|
|
||||||
|
Automatically heats water when solar production exceeds consumption.
|
||||||
|
|
||||||
|
**Enable**: Turn ON `input_boolean.dhw_use_excess_pv_for_aux_heater`
|
||||||
|
|
||||||
|
**Behavior**:
|
||||||
|
- Monitors 3-phase grid power (CT sensors)
|
||||||
|
- Waits for `start_delay` seconds of sufficient export
|
||||||
|
- Heats to `dhw_pv_target_temperature`
|
||||||
|
- Stops after `stop_delay` seconds of insufficient export
|
||||||
|
|
||||||
|
### 3. Bath Boost (Timed)
|
||||||
|
|
||||||
|
Rapid heating with automatic timeout.
|
||||||
|
|
||||||
|
**Trigger**: Call `script.dhw_start_bath_boost` (e.g., from a dashboard button)
|
||||||
|
|
||||||
|
**Behavior**:
|
||||||
|
- Starts timer for configured duration
|
||||||
|
- Turns on circulation pump
|
||||||
|
- Enables aux heater boost
|
||||||
|
- Auto-disables everything when timer expires
|
||||||
|
- Restores pump schedule
|
||||||
|
|
||||||
|
### 4. Normal Boost Mode
|
||||||
|
|
||||||
|
Aux heater supplements heat pump during any thermostat heating call.
|
||||||
|
|
||||||
|
**Enable**: Turn ON `input_boolean.dhw_allow_aux_heater_in_all_modes`
|
||||||
|
|
||||||
|
### 5. Manual Override
|
||||||
|
|
||||||
|
Direct control for testing or emergencies.
|
||||||
|
|
||||||
|
**Enable**: Turn ON `input_boolean.dhw_aux_heater_manual_override`
|
||||||
|
|
||||||
|
**Warning**: Bypasses all safety checks except physical relay. Use with caution.
|
||||||
|
|
||||||
|
## Energy Tracking
|
||||||
|
|
||||||
|
The package includes sensors for monitoring heater usage:
|
||||||
|
|
||||||
|
| Sensor | Purpose |
|
||||||
|
|--------|---------|
|
||||||
|
| `sensor.boiler_resistance_power` | Current power draw (0 or rated power) |
|
||||||
|
| `sensor.boiler_resistance_pv_power` | Power when running on PV excess |
|
||||||
|
| `sensor.boiler_resistance_grid_power` | Power when running on grid |
|
||||||
|
| `sensor.boiler_resistance_total_energy` | Cumulative total energy (kWh) |
|
||||||
|
| `sensor.boiler_resistance_pv_energy` | Cumulative PV energy (kWh) |
|
||||||
|
| `sensor.boiler_resistance_grid_energy` | Cumulative grid energy (kWh) |
|
||||||
|
|
||||||
|
Runtime utility meters are provided with daily, weekly, and monthly cycles for both PV and grid usage.
|
||||||
|
|
||||||
|
## Troubleshooting
|
||||||
|
|
||||||
|
### Heater not turning on
|
||||||
|
|
||||||
|
1. Check `binary_sensor.dhw_use_boiler_aux_heater` state in Developer Tools
|
||||||
|
2. Verify `input_boolean.dhw_allow_aux_heater_usage` is ON
|
||||||
|
3. Check `sensor.heat_pump_auxiliary_heater` is not ON (interlock)
|
||||||
|
4. Verify `sensor.boiler_temp` is below cut-off threshold
|
||||||
|
5. Check automation trace in Automations panel
|
||||||
|
|
||||||
|
### PV mode not activating
|
||||||
|
|
||||||
|
1. Check `binary_sensor.dhw_pv_power_enough_for_aux_heater` state
|
||||||
|
2. Verify all CT sensors show negative values (export)
|
||||||
|
3. Check if export exceeds `(buffer + heater_power) / 3` per phase
|
||||||
|
4. Wait for `start_delay` seconds
|
||||||
|
|
||||||
|
### Preset not applying
|
||||||
|
|
||||||
|
1. Verify `input_select.dhw_boiler_preset` has the expected value
|
||||||
|
2. Check that the corresponding `input_number.dhw_boiler_temp_*` entity exists and has a value
|
||||||
|
3. Check `DHW Boiler Preset Manager` automation trace
|
||||||
|
|
||||||
|
### Heater cycling rapidly
|
||||||
|
|
||||||
|
1. Increase `dhw_pv_excess_usage_stop_delay` to ride through clouds
|
||||||
|
2. Increase `dhw_pv_excess_usage_buffer` for more margin
|
||||||
|
3. Check thermostat tolerance settings
|
||||||
|
|
||||||
|
### Sensor unavailable errors
|
||||||
|
|
||||||
|
The templates include safe defaults:
|
||||||
|
- Temperature sensors default to 100°C (heater stays OFF)
|
||||||
|
- Power sensors default to 0W (no export detected)
|
||||||
|
|
||||||
|
## File Structure
|
||||||
|
|
||||||
|
```
|
||||||
|
excess_pv_boiler/
|
||||||
|
├── use_excess_pv_in_boiler.yaml # Main package file (install this)
|
||||||
|
├── CLAUDE.md # Development context for AI assistants
|
||||||
|
└── README.md # This file
|
||||||
|
```
|
||||||
|
|
||||||
|
## Related Documentation
|
||||||
|
|
||||||
|
- [Home Assistant Generic Thermostat](https://www.home-assistant.io/integrations/generic_thermostat/)
|
||||||
|
- [Home Assistant Packages](https://www.home-assistant.io/docs/configuration/packages/)
|
||||||
|
- [Home Assistant Automations](https://www.home-assistant.io/docs/automation/)
|
||||||
|
- [Home Assistant Scripts](https://www.home-assistant.io/integrations/script/)
|
||||||
|
- [Home Assistant Timer](https://www.home-assistant.io/integrations/timer/)
|
||||||
|
- [Input Select](https://www.home-assistant.io/integrations/input_select/)
|
||||||
|
- [Input Number](https://www.home-assistant.io/integrations/input_number/)
|
||||||
@@ -0,0 +1,520 @@
|
|||||||
|
# Excess PV Boiler Auxiliary Heater Control Package
|
||||||
|
# See README.md for documentation
|
||||||
|
|
||||||
|
input_boolean:
|
||||||
|
dhw_aux_heater_manual_override:
|
||||||
|
name: "DHW Aux Heater Manual Override"
|
||||||
|
icon: mdi:water-boiler
|
||||||
|
|
||||||
|
dhw_allow_aux_heater_usage:
|
||||||
|
name: "DHW Allow Aux Heater Usage"
|
||||||
|
icon: mdi:check-circle
|
||||||
|
|
||||||
|
dhw_use_excess_pv_for_aux_heater:
|
||||||
|
name: "DHW Use Excess PV for Aux Heater"
|
||||||
|
icon: mdi:solar-power
|
||||||
|
|
||||||
|
dhw_allow_aux_heater_in_all_modes:
|
||||||
|
name: "DHW Allow Aux Heater in All Modes"
|
||||||
|
icon: mdi:thermostat
|
||||||
|
|
||||||
|
# Dummy switch for shadow thermostat
|
||||||
|
boiler_pv_dummy_heater:
|
||||||
|
name: "Boiler PV Dummy Heater"
|
||||||
|
icon: mdi:flash
|
||||||
|
|
||||||
|
dhw_bath_boost:
|
||||||
|
name: "DHW Bath Boost"
|
||||||
|
icon: mdi:bath
|
||||||
|
|
||||||
|
input_select:
|
||||||
|
dhw_boiler_preset:
|
||||||
|
name: "DHW Boiler Preset"
|
||||||
|
icon: mdi:thermostat
|
||||||
|
options:
|
||||||
|
- "Normal"
|
||||||
|
- "Eco"
|
||||||
|
- "Boost"
|
||||||
|
- "Sleep"
|
||||||
|
- "Away"
|
||||||
|
- "Off"
|
||||||
|
initial: "Normal"
|
||||||
|
|
||||||
|
timer:
|
||||||
|
bath_time:
|
||||||
|
name: "Bath Time"
|
||||||
|
icon: mdi:timer-outline
|
||||||
|
|
||||||
|
input_number:
|
||||||
|
dhw_aux_heater_cut_off_temperature_threshold:
|
||||||
|
name: "DHW Aux Heater Cut-off Temperature Threshold"
|
||||||
|
min: 50
|
||||||
|
max: 85
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:thermometer-high
|
||||||
|
|
||||||
|
dhw_aux_heater_temperature_threshold:
|
||||||
|
name: "DHW Aux Heater Temperature Threshold"
|
||||||
|
min: 1
|
||||||
|
max: 15
|
||||||
|
step: 0.5
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:thermometer-lines
|
||||||
|
|
||||||
|
dhw_pv_target_temperature:
|
||||||
|
name: "DHW PV Target Temperature"
|
||||||
|
min: 40
|
||||||
|
max: 70
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:solar-power
|
||||||
|
|
||||||
|
dhw_pv_excess_usage_buffer:
|
||||||
|
name: "DHW PV Excess Usage Buffer"
|
||||||
|
min: 0
|
||||||
|
max: 1000
|
||||||
|
step: 50
|
||||||
|
unit_of_measurement: "W"
|
||||||
|
icon: mdi:buffer
|
||||||
|
|
||||||
|
dhw_aux_heater_power:
|
||||||
|
name: "DHW Aux Heater Power"
|
||||||
|
min: 500
|
||||||
|
max: 9000
|
||||||
|
step: 100
|
||||||
|
unit_of_measurement: "W"
|
||||||
|
icon: mdi:lightning-bolt
|
||||||
|
|
||||||
|
dhw_pv_excess_usage_start_delay:
|
||||||
|
name: "DHW PV Excess Start Delay"
|
||||||
|
min: 1
|
||||||
|
max: 300
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "s"
|
||||||
|
icon: mdi:timer-play
|
||||||
|
|
||||||
|
dhw_pv_excess_usage_stop_delay:
|
||||||
|
name: "DHW PV Excess Stop Delay"
|
||||||
|
min: 1
|
||||||
|
max: 300
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "s"
|
||||||
|
icon: mdi:timer-stop
|
||||||
|
|
||||||
|
dhw_boiler_temp_normal:
|
||||||
|
name: "DHW Boiler Normal Temperature"
|
||||||
|
min: 30
|
||||||
|
max: 65
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:thermometer
|
||||||
|
|
||||||
|
dhw_boiler_temp_eco:
|
||||||
|
name: "DHW Boiler Eco Temperature"
|
||||||
|
min: 30
|
||||||
|
max: 60
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:leaf
|
||||||
|
|
||||||
|
dhw_boiler_temp_boost:
|
||||||
|
name: "DHW Boiler Boost Temperature"
|
||||||
|
min: 40
|
||||||
|
max: 70
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:flash
|
||||||
|
|
||||||
|
dhw_boiler_temp_sleep:
|
||||||
|
name: "DHW Boiler Sleep Temperature"
|
||||||
|
min: 25
|
||||||
|
max: 55
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:sleep
|
||||||
|
|
||||||
|
dhw_boiler_temp_away:
|
||||||
|
name: "DHW Boiler Away Temperature"
|
||||||
|
min: 20
|
||||||
|
max: 50
|
||||||
|
step: 1
|
||||||
|
unit_of_measurement: "°C"
|
||||||
|
icon: mdi:home-export-outline
|
||||||
|
|
||||||
|
dhw_bath_boost_duration:
|
||||||
|
name: "DHW Bath Boost Duration"
|
||||||
|
min: 5
|
||||||
|
max: 120
|
||||||
|
step: 5
|
||||||
|
unit_of_measurement: "min"
|
||||||
|
icon: mdi:timer-sand
|
||||||
|
|
||||||
|
climate:
|
||||||
|
- platform: generic_thermostat
|
||||||
|
name: "DHW PV Excess Heating"
|
||||||
|
heater: input_boolean.boiler_pv_dummy_heater
|
||||||
|
target_sensor: sensor.boiler_temp
|
||||||
|
min_temp: 10
|
||||||
|
max_temp: 70
|
||||||
|
cold_tolerance: 1
|
||||||
|
hot_tolerance: 0.5
|
||||||
|
min_cycle_duration:
|
||||||
|
minutes: 2
|
||||||
|
initial_hvac_mode: "off"
|
||||||
|
precision: 0.1
|
||||||
|
|
||||||
|
- platform: generic_thermostat
|
||||||
|
name: "Boiler Temperature"
|
||||||
|
heater: input_boolean.boiler_pv_dummy_heater
|
||||||
|
target_sensor: sensor.boiler_temp
|
||||||
|
min_temp: 10
|
||||||
|
max_temp: 70
|
||||||
|
cold_tolerance: 4.0
|
||||||
|
hot_tolerance: 0
|
||||||
|
min_cycle_duration:
|
||||||
|
minutes: 2
|
||||||
|
|
||||||
|
template:
|
||||||
|
- binary_sensor:
|
||||||
|
- name: "DHW: Use Boiler Aux Heater"
|
||||||
|
unique_id: "dhw_config_use_boiler_aux_heater"
|
||||||
|
state: >
|
||||||
|
{% set manual_on = states('input_boolean.dhw_aux_heater_manual_override') == 'on' %}
|
||||||
|
{% set hp_aux_state = states('sensor.heat_pump_auxiliary_heater') %}
|
||||||
|
{% set hp_aux_off = hp_aux_state in ['off', 'unavailable', 'unknown'] or hp_aux_state != 'on' %}
|
||||||
|
{% set boiler_aux_allowed = states('input_boolean.dhw_allow_aux_heater_usage') == 'on' %}
|
||||||
|
{% set boiler_temp = states('sensor.boiler_temp') | float(100) %}
|
||||||
|
{% set cut_off_temp = states('input_number.dhw_aux_heater_cut_off_temperature_threshold') | float(60) %}
|
||||||
|
{% set boiler_temp_ok = boiler_temp < cut_off_temp %}
|
||||||
|
{# allowed checks if the resistance is permitted to run, mostly to check we're not running both boiler and HP resistance at the same time #}
|
||||||
|
{% set allowed = hp_aux_off and boiler_aux_allowed and boiler_temp_ok %}
|
||||||
|
{# here go various other conditions that influence the decision to run the boiler auxiliary heater #}
|
||||||
|
{# PV Excess to boiler - now using shadow thermostat #}
|
||||||
|
{% set pv_excess = states('input_boolean.dhw_use_excess_pv_for_aux_heater') == 'on' and
|
||||||
|
state_attr('climate.dhw_pv_excess_heating', 'hvac_action') == 'heating' %}
|
||||||
|
{% set thermostat_activity_boost = states('input_boolean.dhw_bath_boost') == 'on' and
|
||||||
|
state_attr('climate.boiler_temperature','hvac_action') == 'heating'%}
|
||||||
|
{% set thermostat_normal_boost = states('input_boolean.dhw_allow_aux_heater_in_all_modes') == 'on' and
|
||||||
|
state_attr('climate.boiler_temperature','hvac_action') == 'heating'%}
|
||||||
|
{{ manual_on or
|
||||||
|
(allowed and (
|
||||||
|
pv_excess or
|
||||||
|
thermostat_activity_boost or
|
||||||
|
thermostat_normal_boost
|
||||||
|
)) }}
|
||||||
|
|
||||||
|
- name: "DHW: PV Power Enough for Aux Heater"
|
||||||
|
unique_id: "dhw_pv_power_enough_for_aux_heater"
|
||||||
|
state: >
|
||||||
|
{% set phase_buffer = states('input_number.dhw_pv_excess_usage_buffer') | float(200) / 3 %}
|
||||||
|
{% set phase_heater_power = states('input_number.dhw_aux_heater_power') | float(3000) / 3 %}
|
||||||
|
{% set turn_on_threshold = -1 * (phase_buffer + phase_heater_power) %}
|
||||||
|
{% set ct1_power = states('sensor.deye_12_external_ct1_power') | float(0) %}
|
||||||
|
{% set ct2_power = states('sensor.deye_12_external_ct2_power') | float(0) %}
|
||||||
|
{% set ct3_power = states('sensor.deye_12_external_ct3_power') | float(0) %}
|
||||||
|
{% if is_state('switch.boiler_heater_relay_switch_0', 'on') %}
|
||||||
|
{{ ct1_power <= 0 and ct2_power <= 0 and ct3_power <= 0 }}
|
||||||
|
{% else %}
|
||||||
|
{{ ct1_power < turn_on_threshold and ct2_power < turn_on_threshold and ct3_power < turn_on_threshold }}
|
||||||
|
{% endif %}
|
||||||
|
device_class: power
|
||||||
|
|
||||||
|
- name: "DHW: Aux Heater Running on PV"
|
||||||
|
unique_id: "dhw_aux_heater_running_on_pv"
|
||||||
|
state: >
|
||||||
|
{{ is_state('switch.boiler_heater_relay_switch_0', 'on') and
|
||||||
|
is_state('binary_sensor.dhw_pv_power_enough_for_aux_heater', 'on') }}
|
||||||
|
|
||||||
|
- name: "DHW: Aux Heater Running on Grid"
|
||||||
|
unique_id: "dhw_aux_heater_running_on_grid"
|
||||||
|
state: >
|
||||||
|
{{ is_state('switch.boiler_heater_relay_switch_0', 'on') and
|
||||||
|
is_state('binary_sensor.dhw_pv_power_enough_for_aux_heater', 'off') }}
|
||||||
|
|
||||||
|
- sensor:
|
||||||
|
- name: "Boiler Resistance Power"
|
||||||
|
unique_id: "boiler_resistance_power"
|
||||||
|
unit_of_measurement: "W"
|
||||||
|
device_class: power
|
||||||
|
state_class: measurement
|
||||||
|
state: >
|
||||||
|
{% if is_state('switch.boiler_heater_relay_switch_0', 'on') %}
|
||||||
|
{{ states('input_number.dhw_aux_heater_power') | float(0) }}
|
||||||
|
{% else %}
|
||||||
|
0
|
||||||
|
{% endif %}
|
||||||
|
|
||||||
|
- name: "Boiler Resistance PV Power"
|
||||||
|
unique_id: "boiler_resistance_pv_power"
|
||||||
|
unit_of_measurement: "W"
|
||||||
|
device_class: power
|
||||||
|
state_class: measurement
|
||||||
|
state: >
|
||||||
|
{% if is_state('binary_sensor.dhw_aux_heater_running_on_pv', 'on') %}
|
||||||
|
{{ states('input_number.dhw_aux_heater_power') | float(0) }}
|
||||||
|
{% else %}
|
||||||
|
0
|
||||||
|
{% endif %}
|
||||||
|
|
||||||
|
- name: "Boiler Resistance Grid Power"
|
||||||
|
unique_id: "boiler_resistance_grid_power"
|
||||||
|
unit_of_measurement: "W"
|
||||||
|
device_class: power
|
||||||
|
state_class: measurement
|
||||||
|
state: >
|
||||||
|
{% if is_state('binary_sensor.dhw_aux_heater_running_on_grid', 'on') %}
|
||||||
|
{{ states('input_number.dhw_aux_heater_power') | float(0) }}
|
||||||
|
{% else %}
|
||||||
|
0
|
||||||
|
{% endif %}
|
||||||
|
|
||||||
|
sensor:
|
||||||
|
- platform: history_stats
|
||||||
|
name: "Boiler Resistance Total Runtime"
|
||||||
|
entity_id: switch.boiler_heater_relay_switch_0
|
||||||
|
state: "on"
|
||||||
|
type: time
|
||||||
|
start: "{{ 0 }}"
|
||||||
|
end: "{{ now() }}"
|
||||||
|
|
||||||
|
- platform: history_stats
|
||||||
|
name: "Boiler Resistance PV Runtime"
|
||||||
|
entity_id: binary_sensor.dhw_aux_heater_running_on_pv
|
||||||
|
state: "on"
|
||||||
|
type: time
|
||||||
|
start: "{{ 0 }}"
|
||||||
|
end: "{{ now() }}"
|
||||||
|
|
||||||
|
- platform: history_stats
|
||||||
|
name: "Boiler Resistance Grid Runtime"
|
||||||
|
entity_id: binary_sensor.dhw_aux_heater_running_on_grid
|
||||||
|
state: "on"
|
||||||
|
type: time
|
||||||
|
start: "{{ 0 }}"
|
||||||
|
end: "{{ now() }}"
|
||||||
|
|
||||||
|
- platform: integration
|
||||||
|
name: "Boiler Resistance Total Energy"
|
||||||
|
source: sensor.boiler_resistance_power
|
||||||
|
unit_prefix: k
|
||||||
|
unit_time: h
|
||||||
|
method: left
|
||||||
|
|
||||||
|
- platform: integration
|
||||||
|
name: "Boiler Resistance PV Energy"
|
||||||
|
source: sensor.boiler_resistance_pv_power
|
||||||
|
unit_prefix: k
|
||||||
|
unit_time: h
|
||||||
|
method: left
|
||||||
|
|
||||||
|
- platform: integration
|
||||||
|
name: "Boiler Resistance Grid Energy"
|
||||||
|
source: sensor.boiler_resistance_grid_power
|
||||||
|
unit_prefix: k
|
||||||
|
unit_time: h
|
||||||
|
method: left
|
||||||
|
|
||||||
|
utility_meter:
|
||||||
|
boiler_resistance_pv_runtime_daily:
|
||||||
|
source: sensor.boiler_resistance_pv_runtime
|
||||||
|
name: "Boiler Resistance PV Runtime Daily"
|
||||||
|
cycle: daily
|
||||||
|
|
||||||
|
boiler_resistance_pv_runtime_weekly:
|
||||||
|
source: sensor.boiler_resistance_pv_runtime
|
||||||
|
name: "Boiler Resistance PV Runtime Weekly"
|
||||||
|
cycle: weekly
|
||||||
|
|
||||||
|
boiler_resistance_pv_runtime_monthly:
|
||||||
|
source: sensor.boiler_resistance_pv_runtime
|
||||||
|
name: "Boiler Resistance PV Runtime Monthly"
|
||||||
|
cycle: monthly
|
||||||
|
|
||||||
|
boiler_resistance_grid_runtime_daily:
|
||||||
|
source: sensor.boiler_resistance_grid_runtime
|
||||||
|
name: "Boiler Resistance Grid Runtime Daily"
|
||||||
|
cycle: daily
|
||||||
|
|
||||||
|
boiler_resistance_grid_runtime_weekly:
|
||||||
|
source: sensor.boiler_resistance_grid_runtime
|
||||||
|
name: "Boiler Resistance Grid Runtime Weekly"
|
||||||
|
cycle: weekly
|
||||||
|
|
||||||
|
boiler_resistance_grid_runtime_monthly:
|
||||||
|
source: sensor.boiler_resistance_grid_runtime
|
||||||
|
name: "Boiler Resistance Grid Runtime Monthly"
|
||||||
|
cycle: monthly
|
||||||
|
|
||||||
|
script:
|
||||||
|
dhw_start_bath_boost:
|
||||||
|
alias: "DHW Start Bath Boost"
|
||||||
|
description: "Starts the bath boost timer with the configured duration"
|
||||||
|
icon: mdi:bath
|
||||||
|
sequence:
|
||||||
|
- action: timer.start
|
||||||
|
target:
|
||||||
|
entity_id: timer.bath_time
|
||||||
|
data:
|
||||||
|
duration: "{{ (states('input_number.dhw_bath_boost_duration') | int(30)) * 60 }}"
|
||||||
|
|
||||||
|
automation:
|
||||||
|
- alias: DHW Boiler Heater Relay Automation
|
||||||
|
description: >-
|
||||||
|
This automation makes sure the boiler auxiliary heater only works when the
|
||||||
|
boost is required and the heatpump aux heater is not on
|
||||||
|
triggers:
|
||||||
|
- trigger: state
|
||||||
|
entity_id:
|
||||||
|
- binary_sensor.dhw_use_boiler_aux_heater
|
||||||
|
conditions: []
|
||||||
|
actions:
|
||||||
|
- if:
|
||||||
|
- condition: state
|
||||||
|
entity_id: binary_sensor.dhw_use_boiler_aux_heater
|
||||||
|
state: "on"
|
||||||
|
then:
|
||||||
|
- action: switch.turn_on
|
||||||
|
metadata: { }
|
||||||
|
target:
|
||||||
|
entity_id: switch.boiler_heater_relay_switch_0
|
||||||
|
data: { }
|
||||||
|
else:
|
||||||
|
- action: switch.turn_off
|
||||||
|
metadata: { }
|
||||||
|
target:
|
||||||
|
entity_id: switch.boiler_heater_relay_switch_0
|
||||||
|
data: { }
|
||||||
|
mode: single
|
||||||
|
|
||||||
|
- alias: DHW Manage PV Thermostat
|
||||||
|
description: Controls shadow thermostat based on PV excess availability
|
||||||
|
mode: restart
|
||||||
|
trigger:
|
||||||
|
# Trigger when PV power becomes sufficient (with delay)
|
||||||
|
- platform: state
|
||||||
|
entity_id: binary_sensor.dhw_pv_power_enough_for_aux_heater
|
||||||
|
to: "on"
|
||||||
|
for:
|
||||||
|
seconds: "{{ states('input_number.dhw_pv_excess_usage_start_delay') | int(60) }}"
|
||||||
|
id: "turn_on"
|
||||||
|
|
||||||
|
# Trigger when PV power becomes insufficient (with delay)
|
||||||
|
- platform: state
|
||||||
|
entity_id: binary_sensor.dhw_pv_power_enough_for_aux_heater
|
||||||
|
to: "off"
|
||||||
|
for:
|
||||||
|
seconds: "{{ states('input_number.dhw_pv_excess_usage_stop_delay') | int(60) }}"
|
||||||
|
id: "turn_off"
|
||||||
|
action:
|
||||||
|
- choose:
|
||||||
|
- conditions:
|
||||||
|
- condition: state
|
||||||
|
entity_id: input_boolean.dhw_use_excess_pv_for_aux_heater
|
||||||
|
state: "on"
|
||||||
|
- condition: trigger
|
||||||
|
id: "turn_on"
|
||||||
|
sequence:
|
||||||
|
- service: climate.set_temperature
|
||||||
|
target:
|
||||||
|
entity_id: climate.dhw_pv_excess_heating
|
||||||
|
data:
|
||||||
|
temperature: "{{ states('input_number.dhw_pv_target_temperature') | float }}"
|
||||||
|
hvac_mode: "heat"
|
||||||
|
|
||||||
|
- conditions:
|
||||||
|
- condition: trigger
|
||||||
|
id: "turn_off"
|
||||||
|
sequence:
|
||||||
|
- service: climate.set_hvac_mode
|
||||||
|
target:
|
||||||
|
entity_id: climate.dhw_pv_excess_heating
|
||||||
|
data:
|
||||||
|
hvac_mode: "off"
|
||||||
|
|
||||||
|
- alias: DHW Boiler Preset Manager
|
||||||
|
description: >-
|
||||||
|
Sets the boiler thermostat temperature based on the selected preset
|
||||||
|
and the user-configurable temperature for that preset.
|
||||||
|
Also toggles dhw_bath_boost when Boost preset is selected.
|
||||||
|
mode: restart
|
||||||
|
triggers:
|
||||||
|
- trigger: state
|
||||||
|
entity_id:
|
||||||
|
- input_select.dhw_boiler_preset
|
||||||
|
- trigger: state
|
||||||
|
entity_id:
|
||||||
|
- input_number.dhw_boiler_temp_normal
|
||||||
|
- input_number.dhw_boiler_temp_eco
|
||||||
|
- input_number.dhw_boiler_temp_boost
|
||||||
|
- input_number.dhw_boiler_temp_sleep
|
||||||
|
- input_number.dhw_boiler_temp_away
|
||||||
|
actions:
|
||||||
|
- choose:
|
||||||
|
- conditions:
|
||||||
|
- condition: state
|
||||||
|
entity_id: input_select.dhw_boiler_preset
|
||||||
|
state: "Off"
|
||||||
|
sequence:
|
||||||
|
- action: climate.set_hvac_mode
|
||||||
|
target:
|
||||||
|
entity_id: climate.boiler_temperature
|
||||||
|
data:
|
||||||
|
hvac_mode: "off"
|
||||||
|
- action: input_boolean.turn_off
|
||||||
|
target:
|
||||||
|
entity_id: input_boolean.dhw_bath_boost
|
||||||
|
default:
|
||||||
|
- action: climate.set_temperature
|
||||||
|
target:
|
||||||
|
entity_id: climate.boiler_temperature
|
||||||
|
data:
|
||||||
|
temperature: >
|
||||||
|
{% set preset = states('input_select.dhw_boiler_preset') | lower %}
|
||||||
|
{{ states('input_number.dhw_boiler_temp_' ~ preset) | float(50) }}
|
||||||
|
hvac_mode: "heat"
|
||||||
|
- if:
|
||||||
|
- condition: state
|
||||||
|
entity_id: input_select.dhw_boiler_preset
|
||||||
|
state: "Boost"
|
||||||
|
then:
|
||||||
|
- action: input_boolean.turn_on
|
||||||
|
target:
|
||||||
|
entity_id: input_boolean.dhw_bath_boost
|
||||||
|
else:
|
||||||
|
- action: input_boolean.turn_off
|
||||||
|
target:
|
||||||
|
entity_id: input_boolean.dhw_bath_boost
|
||||||
|
|
||||||
|
- alias: DHW Bath Time
|
||||||
|
description: >-
|
||||||
|
Manages bath boost lifecycle: enables boost + ACM pump when timer starts,
|
||||||
|
restores schedule and disables both when timer finishes.
|
||||||
|
triggers:
|
||||||
|
- trigger: state
|
||||||
|
entity_id:
|
||||||
|
- timer.bath_time
|
||||||
|
conditions: []
|
||||||
|
actions:
|
||||||
|
- if:
|
||||||
|
- condition: state
|
||||||
|
entity_id: timer.bath_time
|
||||||
|
state: active
|
||||||
|
then:
|
||||||
|
- action: switch.turn_on
|
||||||
|
target:
|
||||||
|
entity_id: switch.acm_pump_switch
|
||||||
|
- action: input_boolean.turn_on
|
||||||
|
target:
|
||||||
|
entity_id: input_boolean.dhw_bath_boost
|
||||||
|
else:
|
||||||
|
- action: scheduler.run_action
|
||||||
|
data:
|
||||||
|
entity_id: switch.schedule_f403a3
|
||||||
|
- action: switch.turn_off
|
||||||
|
target:
|
||||||
|
entity_id: switch.acm_pump_switch
|
||||||
|
- action: input_boolean.turn_off
|
||||||
|
target:
|
||||||
|
entity_id: input_boolean.dhw_bath_boost
|
||||||
|
mode: single
|
||||||