# CLAUDE.md - Development Context for Excess PV Boiler Control
|
||||
|
||||
## Project Purpose
|
||||
|
||||
This Home Assistant package controls an auxiliary electric heater installed in a DHW (Domestic Hot Water) boiler. It works alongside a heat pump to provide:
|
||||
- **Preset-based temperature control** with user-adjustable temperatures per preset
|
||||
- **PV excess utilization** to use surplus solar power instead of exporting
|
||||
- **Bath boost** with configurable timer for rapid hot water
|
||||
- **Manual override** for emergency/testing scenarios
|
||||
|
||||
## Architecture
|
||||
|
||||
```
|
||||
[Solar Inverter] --> sensor.deye_12_external_ct*_power (3-phase grid power)
|
||||
|
|
||||
[binary_sensor.dhw_pv_power_enough_for_aux_heater]
|
||||
|
|
||||
[automation: DHW Manage PV Thermostat]
|
||||
|
|
||||
[climate.dhw_pv_excess_heating] (shadow thermostat)
|
||||
|
|
||||
[binary_sensor.dhw_use_boiler_aux_heater] <-- [manual override]
|
||||
| <-- [boost modes]
|
||||
[automation: DHW Boiler Heater Relay]
|
||||
|
|
||||
[switch.boiler_heater_relay_switch_0] (physical relay)
|
||||
|
||||
[input_select.dhw_boiler_preset] --> [automation: DHW Boiler Preset Manager]
|
||||
[input_number.dhw_boiler_temp_*] |
|
||||
v
|
||||
[climate.boiler_temperature] (main thermostat)
|
||||
|
||||
[script.dhw_start_bath_boost] --> [timer.bath_time] --> [automation: DHW Bath Time]
|
||||
[input_number.dhw_bath_boost_duration] |
|
||||
v
|
||||
[input_boolean.dhw_bath_boost] + [switch.acm_pump_switch]
|
||||
```
|
||||
|
||||
## Key Entities
|
||||
|
||||
### Input Booleans (Modes/Toggles)
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `input_boolean.dhw_aux_heater_manual_override` | Force heater ON regardless of conditions |
|
||||
| `input_boolean.dhw_allow_aux_heater_usage` | Master enable for aux heater |
|
||||
| `input_boolean.dhw_use_excess_pv_for_aux_heater` | Enable PV excess mode |
|
||||
| `input_boolean.dhw_allow_aux_heater_in_all_modes` | Allow boost in normal thermostat mode |
|
||||
| `input_boolean.boiler_pv_dummy_heater` | Virtual switch for shadow thermostat |
|
||||
| `input_boolean.dhw_bath_boost` | Bath boost active flag (managed by automations) |
|
||||
|
||||
### Input Select (Presets)
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `input_select.dhw_boiler_preset` | Active boiler preset: Normal, Eco, Boost, Sleep, Away, Off |
|
||||
|
||||
### Timer
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `timer.bath_time` | Countdown timer for bath boost duration |
|
||||
|
||||
### Input Numbers (Thresholds)
|
||||
| Entity | Purpose | Range |
|
||||
|--------|---------|-------|
|
||||
| `input_number.dhw_aux_heater_cut_off_temperature_threshold` | Max temp before heater stops | 50-85°C |
|
||||
| `input_number.dhw_aux_heater_temperature_threshold` | Hysteresis threshold | 1-15°C |
|
||||
| `input_number.dhw_pv_target_temperature` | Target temp for PV heating | 40-70°C |
|
||||
| `input_number.dhw_pv_excess_usage_buffer` | Buffer power before triggering | 0-1000W |
|
||||
| `input_number.dhw_aux_heater_power` | Heater power rating | 500-9000W |
|
||||
| `input_number.dhw_pv_excess_usage_start_delay` | Delay before starting PV mode | 1-300s |
|
||||
| `input_number.dhw_pv_excess_usage_stop_delay` | Delay before stopping PV mode | 1-300s |
|
||||
|
||||
### Input Numbers (Preset Temperatures)
|
||||
| Entity | Purpose | Range |
|
||||
|--------|---------|-------|
|
||||
| `input_number.dhw_boiler_temp_normal` | Normal preset target temperature | 30-65°C |
|
||||
| `input_number.dhw_boiler_temp_eco` | Eco preset target temperature | 30-60°C |
|
||||
| `input_number.dhw_boiler_temp_boost` | Boost preset target temperature | 40-70°C |
|
||||
| `input_number.dhw_boiler_temp_sleep` | Sleep preset target temperature | 25-55°C |
|
||||
| `input_number.dhw_boiler_temp_away` | Away preset target temperature | 20-50°C |
|
||||
| `input_number.dhw_bath_boost_duration` | Duration for bath boost timer | 5-120 min |
|
||||
|
||||
### Scripts
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `script.dhw_start_bath_boost` | Starts `timer.bath_time` with duration from `dhw_bath_boost_duration` |
|
||||
|
||||
### Climate (Generic Thermostats)
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `climate.dhw_pv_excess_heating` | Shadow thermostat for PV excess mode |
|
||||
| `climate.boiler_temperature` | Main boiler thermostat (target set by preset manager) |
|
||||
|
||||
### Automations
|
||||
| Entity | Purpose |
|
||||
|--------|---------|
|
||||
| `DHW Boiler Heater Relay Automation` | Switches physical relay based on decision sensor |
|
||||
| `DHW Manage PV Thermostat` | Controls shadow thermostat based on PV availability |
|
||||
| `DHW Boiler Preset Manager` | Syncs preset selection + temperatures to thermostat, toggles bath boost |
|
||||
| `DHW Bath Time` | Manages bath boost lifecycle: pump + boost on/off with timer |
|
||||
|
||||
### External Entities (Not Defined in Package)
|
||||
These must exist in your HA instance from other integrations or manual UI setup:
|
||||
|
||||
| Entity | Source | Purpose | Fallback if Unavailable |
|
||||
|--------|--------|---------|------------------------|
|
||||
| `sensor.boiler_temp` | Heat pump / temperature probe | Boiler water temperature | 100 (prevents running) |
|
||||
| `sensor.deye_12_external_ct1_power` | Deye inverter integration | Phase 1 grid power (negative = export) | 0 |
|
||||
| `sensor.deye_12_external_ct2_power` | Deye inverter integration | Phase 2 grid power | 0 |
|
||||
| `sensor.deye_12_external_ct3_power` | Deye inverter integration | Phase 3 grid power | 0 |
|
||||
| `sensor.heat_pump_auxiliary_heater` | Heat pump integration | HP aux heater state | treated as 'off' |
|
||||
| `switch.boiler_heater_relay_switch_0` | Relay device (Shelly, etc.) | Physical heater control | N/A |
|
||||
| `switch.acm_pump_switch` | Pump relay/smart plug | DHW circulation pump | N/A |
|
||||
| `switch.schedule_f403a3` | Scheduler integration | Pump schedule to restore after boost | N/A |
|
||||
|
||||
## Decision Logic
|
||||
|
||||
### binary_sensor.dhw_use_boiler_aux_heater
|
||||
This is the main decision sensor. It turns ON when:
|
||||
1. **Manual override** is ON, OR
|
||||
2. **All conditions met**:
|
||||
- Heat pump aux heater is OFF
|
||||
- Boiler aux usage is allowed
|
||||
- Boiler temp is below cut-off threshold
|
||||
- AND one of:
|
||||
- PV excess mode active AND shadow thermostat is heating
|
||||
- Bath boost active AND main thermostat is heating
|
||||
- All-modes boost enabled AND main thermostat is heating
|
||||
|
||||
### binary_sensor.dhw_pv_power_enough_for_aux_heater
|
||||
Determines if there's enough solar export to run the heater:
|
||||
- **When heater is OFF**: All 3 phases must export > (buffer + heater_power) / 3
|
||||
- **When heater is ON**: All 3 phases must still be exporting (<=0W import)
|
||||
|
||||
### Preset Manager Flow
|
||||
1. User selects preset from `input_select.dhw_boiler_preset`
|
||||
2. Automation reads corresponding `input_number.dhw_boiler_temp_<preset>` value
|
||||
3. Sets `climate.boiler_temperature` to that target + heat mode (or off for "Off" preset)
|
||||
4. Toggles `input_boolean.dhw_bath_boost` on/off based on whether Boost is selected
|
||||
5. If user changes a preset temperature input_number, automation re-applies current preset
|
||||
|
||||
### Bath Boost Flow
|
||||
1. User calls `script.dhw_start_bath_boost` (e.g., from a dashboard button)
|
||||
2. Script starts `timer.bath_time` with duration from `input_number.dhw_bath_boost_duration`
|
||||
3. `DHW Bath Time` automation detects timer active: turns on pump + bath boost
|
||||
4. Timer finishes: automation restores pump schedule + turns off boost
|
||||
|
||||
## Common Modifications
|
||||
|
||||
### Changing Preset Temperatures
|
||||
Adjust via dashboard sliders at runtime (no YAML edit needed).
|
||||
The `input_number.dhw_boiler_temp_*` entities store each preset's temperature.
|
||||
|
||||
### Adding New Presets
|
||||
1. Add option to `input_select.dhw_boiler_preset`
|
||||
2. Add corresponding `input_number.dhw_boiler_temp_<name>` (name must be lowercase match)
|
||||
3. The preset manager automation uses dynamic entity resolution, so no automation changes needed
|
||||
|
||||
### Changing Power Thresholds
|
||||
Adjust via dashboard at runtime:
|
||||
- `dhw_pv_excess_usage_buffer`: Increase for more conservative PV triggering
|
||||
- `dhw_aux_heater_power`: Match to actual heater rating
|
||||
|
||||
### Adjusting Timing
|
||||
Adjust via dashboard at runtime:
|
||||
- `dhw_pv_excess_usage_start_delay`: Increase to avoid rapid cycling
|
||||
- `dhw_pv_excess_usage_stop_delay`: Increase to ride through clouds
|
||||
- `dhw_bath_boost_duration`: Duration of bath boost timer
|
||||
|
||||
### Adding New Heating Modes
|
||||
Edit template section, add new condition in `binary_sensor.dhw_use_boiler_aux_heater` alongside `pv_excess`, `thermostat_activity_boost`, etc.
|
||||
|
||||
## Testing/Validation
|
||||
|
||||
1. **YAML Syntax**: Run `yamllint *.yaml` or use HA's configuration check
|
||||
2. **Entity References**: Ensure all `states()` calls reference defined entities
|
||||
3. **Default Fallbacks**: Verify all `float()` filters have appropriate defaults:
|
||||
- Temperature sensors: `float(100)` (fail-safe: heater OFF)
|
||||
- Power sensors: `float(0)` (fail-safe: no export detected)
|
||||
- Input numbers: `float(<sensible_default>)`
|
||||
|
||||
## File Structure
|
||||
|
||||
| File | Purpose |
|
||||
|------|---------|
|
||||
| `use_excess_pv_in_boiler.yaml` | **Main package file** - install this in HA packages directory |
|
||||
| `CLAUDE.md` | Development context for AI assistants |
|
||||
| `README.md` | User-facing documentation |
|
||||
|
||||
## Safety Considerations
|
||||
|
||||
1. **Never run both heaters**: Template checks `sensor.heat_pump_auxiliary_heater != 'on'`
|
||||
2. **Temperature cut-off**: Hard limit prevents overheating
|
||||
3. **Unavailable sensors**: Default to safe values (temp=100, power=0)
|
||||
4. **Manual override**: Bypasses all checks - use with caution
|
||||
5. **Bath boost timer**: Auto-disables boost when timer expires
|
||||